Permit Number: T21CM02471
Parcel: 134130580

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - T21CM02471
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/22/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/22/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

The existing electrical service secondary conductors are installed Underground. The revised electrical service upgrade calls for Overhead utility service conductors.

Per 2018 IBC Amendments City of Tucson requires the new utility service drop to remain as an U.G. installation.

Section 112.1.1 Service conductors. All service conductors, power and communication, shall be installed underground for all new construction. The requirement for underground conductors may be waived by the Building Official where: 1. Existing buildings on the block are served with overhead conductors or where a lot to be constructed upon is one of three or fewer abutting vacant lots making up less than 40 percent of the total acreage of the block (not including street or right-of-way) or where a vacant area is less than 60,000 square feet. 2. The installation, when compared to the use of overhead conductors, would create a hazard or not be feasible. A feasibility study will be required at the time the request for waiver is made.

Ref; 2018 IBC, 2017 NEC, and all adopted Amendments to these codes.
05/09/2023 PDSD Application Completeness Express REVIEW COMPLETED