Permit Number: DP22-0267
Parcel: 14111459B

Review Status: Requires Resubmit

Review Details: DEVELOPMENT PACKAGE REVIEW v.2

Permit Number - DP22-0267
Review Name: DEVELOPMENT PACKAGE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/27/2023 NPPO APPROVED
01/27/2023 Site Landscape APPROVED
03/10/2023 CDRC Post Review Express PENDING ASSIGNMENT
02/27/2023 Site Engineering REQUIRES RESUBMIT 1. Previous comment 2 not fully addressed. Note 17 on page 2 under paving and grading notes now reads (6-9 inches is measured from the top of the ground to cover) – The wording is confusing, please clarify to read measured from the top of ground cover.
2. Per TSM section 8-01.4.0.G – Use of APCs for multi-family, commercial, or industrial development requires prior approval from ES. Please reach out for Andy Vera for approval.
Andy Vera
City of Tucson -Environmental Services
Accounts Representative Supervisor
(520) 837-3798


Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov
02/22/2023 Site Zoning REQUIRES RESUBMIT FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: 8605 E OLD VAIL RD
Development Package (2nd Review)
DP22-0267
TRANSMITTAL DATE: February 22, 2023



COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is September 9, 2023 .

SECTION 2-06.0.0: DEVELOPMENT PACKAGE (TENTATIVE PLATS AND SITE PLANS)

2-06.4.7.A.6.a - List additional applications and overlays, by case number (if applicable), in lower right corner of each sheet. As a general note provide the type of application processed or overlays applicable, a statement that the project meets the criteria/conditions of the additional application or overlay, the case number, date of approval, what was approved, and the conditions of approval, if any.

This comment is still applicable please provide a note that states “this project is subject to ordinance 6143 adopted December 17, 1984 C9-64-84.”
1. COMMENT: 2-06.4.7.A.6.a - Provide the information noted by the standard above for the Annexation C9-64-84 insure this project is meeting the annexation conditions.


2-06.4.7.A.8.a - Floor area for each building;
This comment is still applicable please remove the by other, provide a note that the structures will be by others.
2. COMMENT: 2-06.4.7.A.8.a - Clarify what by others, if these structures are not part of this Development package please remove, If they are provide the necessary information.






2-06.4.9 - Information on Proposed Development
The following information on the proposed project shall be shown on the drawing or added as notes.


2-06.4.9.F - All existing zoning classifications on and adjacent to the project (including across any adjacent right-of-way) shall be indicated on the drawing with zoning boundaries clearly defined. If the property is being rezoned, use those boundaries and classifications. The basis for this requirement is that some zoning requirements on a project are based on the zoning classification of adjacent property. Also, in some instances, each zone has to be taken into consideration on property that is split by two or more zoning classifications, as each may have different requirements.
This comment is still applicable provide the zoning classification on the site plan.
3. COMMENT: 2-06.4.9.F - Provide the information noted by the standard above.


2-06.4.9.J - If street dedication is not required or proposed and the project site is adjacent to a Major Street or Route, draw the Major Street right-of-way lines for those streets. (Add the MS&R future sidewalk, right-of-way lines, sight visibility triangles, etc.)
This comment is still applicable the right of way dimension on old vail rd 90ft provide in the link below is the paving plans. https://www.tucsonaz.gov/apps/maps-and-records/construction-plans/details/I-86-069
4. COMMENT: 2-06.4.9.J - Provide the information noted by the standard above.


2-06.4.9.Q - Provide the square footage and the height of each commercial, industrial, or business structure and the specific use proposed within the footprint of the building(s).
Please provide the information noted by the standard above on the office building.
5. COMMENT: 2-06.4.9.Q - Provide the information noted by the standard above


2-06.4.9.R - Show on-site pedestrian circulation and refuge utilizing location and the design criteria in Section 7-01.0.0, Pedestrian Access, of the Technical Standards Manual.
This comment is still applicable. Clarify if this are is to be open to the public.
6. COMMENT: 2-06.4.9.R - Clarify if the area to the north is a public area. If not provide barrier.






***For additional information on the any standard presented in this memo, please refer to the City of Tucson “Unified Development Code” – Administrative Manual Section 2-06 or Technical Standards noted in the comments. https://www.tucsonaz.gov/pdsd/all-codes-plans-determinations



If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov
RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
03/10/2023 External Reviewers - Pima County Addressing REVIEW COMPLETED Good afternoon,



This project does not require review by Pima County Addressing.





Thank you



Nicholas Jordan

Site Review Project Manager - Addressing Official

Pima County Development Services Department

201 N Stone AV – 1st Floor

Tucson, AZ 85701

(520) 724-9623
01/30/2023 Fire New Construction REVIEW COMPLETED