Permit Number: DP22-0218
Parcel: 137276510

Review Status: Requires Resubmit

Review Details: DEVELOPMENT PACKAGE REVIEW v.2

Permit Number - DP22-0218
Review Name: DEVELOPMENT PACKAGE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/12/2023 Site Engineering APPROVED
05/01/2023 Site Zoning APPROVED
05/18/2023 CDRC Post Review Express PENDING ASSIGNMENT
05/18/2023 Commercial Plumbing REQUIRES RESUBMIT Comment not resolved. Sheet 3 of 11 still refers to the existing backflow assembly located on the north side of the building as a backwater valve and sheet 5 of 11 points to the proposed installation of a backwater valve at the same location. [Second comment: Comment not addressed.] [Initial comment: Revise the references to a backwater valve on sheets 3 of 11 and 5 of 11. Backwater valves are used to prevent sewage from backing up into a building and are not used for water service. Reduced pressure backflow prevention assemblies are required to be installed directly after the water meter for buildings that have food service facilities. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf]
04/18/2023 CDRC Application Completeness Express REVIEW COMPLETED