Review Details: DEVELOPMENT PACKAGE REVIEW v.1

Permit Number - DP21-0108
Review Name: DEVELOPMENT PACKAGE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/08/2022 Fire New Construction APPROVED
12/06/2022 OK to Submit - Zoning Fast APPROVED
12/07/2022 Site Engineering APPROVED
12/08/2022 Site Zoning APPROVED
12/08/2022 NPPO NOT REQUIRED
12/07/2022 OK to Submit - External Reviewer PC Addressing Fast NOT REQUIRED
12/08/2022 ROW Engineering Review NOT REQUIRED
12/08/2022 Site Landscape NOT REQUIRED
12/08/2022 CDRC Post Review Express PENDING ASSIGNMENT
12/08/2022 Commercial Plumbing REQUIRES RESUBMIT 1. Reduced pressure backflow prevention assemblies are required to be installed directly after the water meter for buildings that have food service facilities. The reduced pressure backflow prevention assemblies are required to be installed in locations accessible to Tucson Water. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf
2. Correct the keynote 7 on sheet C6.0, located within the building footprint. It refers to a 4” fire service but points to the 2” domestic water service. Reference: Section 107.2.1, IBC 2018.
3. Provide the rim elevation of the next upstream sanitary manhole, 8638-01. Determine the need for a backwater valve per Section 714.1, IPC 2018, as amended by the City of Tucson.
12/01/2022 CDRC Application Completeness Express REVIEW COMPLETED
12/07/2022 CDRC Review Coordinator Express REVIEW COMPLETED
12/02/2022 OK to Submit - Engineering Fast REVIEW COMPLETED