Permit Number: DP20-0159
Parcel: 14111030B

Review Status: Requires Resubmit

Review Details: DEVELOPMENT PACKAGE REVIEW v.1

Permit Number - DP20-0159
Review Name: DEVELOPMENT PACKAGE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/12/2023 Commercial Plumbing APPROVED
07/03/2023 Site Engineering APPROVED
06/23/2023 Site Landscape APPROVED Landscape is misspelled on all the details
07/12/2023 CDRC Post Review Express PENDING ASSIGNMENT
07/10/2023 External Reviewers - Tucson Airport Authority REQUIRES RESUBMIT July 7, 2023
Planning and Development Services
City of Tucson
201 North Stone Avenue
Tucson, AZ. 85701
RE: DP20-0159, SITE/GRADING - Optimum Inc, new building and driveway / 8500 E Old Vail
Rd, Tucson AZ 85747, Received June 15, 2023
To whom this may concern,
Thank you for the opportunity to comment on DP20-0159, the development plan for Optimum
Inc, new building and driveway at 8500 E Old Vail Rd. This development is located in the S.W.
corner of the S.E. quarter of Section 21, Township 15S, Range 15E, of the Gila and Salt River
Meridian. The development site occupies parcel number 141-11-030B, covers approximately
5.08 ± acres, and is zoned as Heavy Industrial Zone (I-2). The nearest major roadway
intersection is E Old Vail Rd and S Rita Rd, approximately 3600 feet to the southeast of the
subject development.
This site does lie within FAA Part 77 airspace.
The Tucson Airport is requiring a resubmit of this project. These conditions must be included in
the development plan document and shall be identified in the general notes section of all future
plans submitted to the City of Tucson for review.
Conditions of approval:
1. “According to the Federal Aviation Administration (FAA) Notice Criteria Tool, this project
area is located in proximity to a navigation facility and could impact navigation signal
reception. This proposed structure exceeds an instrument approach area by 42 feet and
an aeronautical study is needed to determine if it will exceed a standard of subpart C of
14CFR Part 77. As this project develops, all applicants must file FAA Form 7460 with
the FAA at least 45 days before construction activities begin unless FAA staff, with the
Obstruction Evaluation / Airport Airspace Analysis (OE/AAA), provides the project
applicant with written communication that filing FAA Form 7460 is not required. It is
highly recommended that the applicant file earlier than 45 days to provide the applicant
with sufficient time to respond to any concerns identified by the FAA. Note also that
cranes to be used during all development or construction activities must also be
identified with Form 7460. Please file Form 7460 at
https://oeaaa.faa.gov/oeaaa/external/portal.jsp.”
Please do not hesitate to contact me if you have any questions or concerns regarding this
comment letter. I can be reached by email at srobidoux@flytucson.com or by telephone at 520-
573-4811.
Respectfully,
Scott Robidoux, C.M.
Manager of Planning
07/06/2023 ROW Engineering Review REQUIRES RESUBMIT DP20-0159 (8500 E OLD VAIL RD TUCSON, AZ 85747)

Please resubmit revised drawings along with a detailed response letter which states how all comments were addressed.

Comments:

1. The Tucson Street Design Guide offers the option to use a smaller 15’ curb radius on the proposed curb returns on the eastern side of the property (SDG 5-10). Smaller radii are safer for pedestrians. The smallest feasible radius should be used.
2. 10-01.3.3.D.1.d - Lateral transitions in sidewalk shall be no sharper than 3:1. Where the sidewalk jogs laterally near the new 25’ driveway, please show that it meets this standard. See P. A. G. SD 207 for an illustration.
3. Please repair any sidewalk in the ROW that has become uneven over time or heaved by tree roots.
4. The Subdivision plat seems to show a 60’ utility easement running very roughly parallel to Old Vail Rd. If the easement still exists, please show it on the plans.

Faffs Riederer
Faffs.Riederer@tucsonaz.gov

Abbreviations: City of Tucson Code (COTC), Unified Development Code (UDC) Administrative Manual (AM), Technical Standards Manual (TSM), Street Design Guide (SDG), Pima Association of Governments Standard Details (P. A. G. SD), Access Management Guidelines (AMG), Major Streets and Routes Plan (MS&R).
06/23/2023 Site Zoning REQUIRES RESUBMIT CDRC TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: Optimum Inc
Development Package (1st Revision – 1st Review)
DP20-0159

TRANSMITTAL DATE: June 23, 2023

DUE DATE: June 14, 2023

COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also, compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

The review comments include the applicable Administrative Manual section number and the following paragraph is the actual comment related to the specific item that must be addressed. If you need to review the sections listed below click on the link or copy it in the address bar of your internet program. http://www.amlegal.com/nxt/gateway.dll/Arizona/tucson_az_udc/administrativemanual?f=templates$fn=default.htm$3.0$vid=amlegal:tucson_udc_az

This link will take you directly to the section used for the standards review. The UDC & TSM requirements are in the Unified Development Code and can be viewed at the same web link as above

Section 3.3.3.G.5.c UDC, an applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One-year Expiration date is June 13, 2024.

2-06.4.7 - General Notes
The following general notes are required. Additional notes specific to each plan are required where applicable.

2-06.4.7.A - Zoning and Land Use Notes

1. 2-06.4.7.A.4 - The use called out under GENERAL DEVELOPMENT PLAN NOTE 3 is Construction Services, but under “UNIFORM DEVELOPMENT CODE” “BUILDING USE: 2 PRINCIPLE USES:” you list “INDUSTRIAL USE GROUP (EXISTING)” “INDUSTRIAL USE GROUP, WAREHOUSE” & “COMMERICAL SERVICES , OFFICE” clarify what the use is. “INDUSTRIAL USE GROUP (EXISTING)” is not a use but a use group. “INDUSTRIAL USE GROUP, WAREHOUSE”, warehouse is not a use in the Industrial Use Group. If you are proposing 2 principles uses than separate Certificate of Occupancies are required.

2. 2-06.4.7.A.4 – As you are proposing to demolish Bldg. #1 remove the reference to Building #1 from under “UNIFORM DEVELOPMENT CODE” “BUILDING USE: 2 PRINCIPLE USES:”.

2-06.4.7.A.8 - For development package documents provide:

3. COMMENT: 2-06.4.7.A.8.a - As you are proposing to demolish Bldg. #1 remove the reference to Building #1 from under “BUILDING DATA”.

4. COMMENT: 2-06.4.7.A.8.a – Under “BUILDING DATA”, “BUILDING #2 (EXISTING)” & “BUILDING #3 (EXISTING)” and “BUILDING #4 (NEW)” you show the use as “INDUSTRIAL USE / CONSTRUCTION SERVICE”, Construction Service is not a use within the Industrial Use Group, clarify what use group and use you area proposing for these buildings.

5. COMMENT: 2-06.4.7.A.8.a – Under “BUILDING DATA”, “BUILDING #5 (NEW)” the use is listed as “OFFICE/COMMERCIAL SERVICE USE GROUP”, Office use does not the use listed under GENERAL DEVELOPMENT PLAN NOTE 3, clarify what you use is.

2-06.4.9 - Information on Proposed Development
The following information on the proposed project shall be shown on the drawing or added as notes.

6. COMMENT: 2-06.4.9.H.5.a – Until the use is clarified Zoning cannot verify the required number of vehicle parking spaces. Based on a construction services use the vehicle parking space calculation is not correct. Construction services is parked at 1 space per 300 square feet of gross floor area. This includes all buildings on site including storage containers. Until the proposed use is clarified the required number of vehicle parking spaces cannot be verified.

7. COMMENT: 2-06.4.9.H.5.d - Until the use is clarified Zoning cannot verify the required number of short- & long-term bicycle parking space.

8. COMMENT: 2-06.4.9.H.5.d - Zoning was not able to find the required short-term bicycle parking on the plan, clarify the location.

If you have any questions about this transmittal, please contact Nicholas Martell at Nicholas.Martell@tucsonaz.gov.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package & detailed response letter.
06/07/2023 CDRC Application Completeness Express REVIEW COMPLETED
06/22/2023 CDRC Review Coordinator Express REVIEW COMPLETED
06/30/2023 Fire New Construction REVIEW COMPLETED
06/23/2023 NPPO REVIEW COMPLETED
06/07/2023 OK to Submit - Engineering Fast REVIEW COMPLETED
06/07/2023 OK to Submit - Landscape Fast REVIEW COMPLETED
06/14/2023 OK to Submit - Zoning Fast REVIEW COMPLETED