Review Status: Requires Resubmit

Review Details: CIP - DEV SITE + COMM STRUCTURE - FINAL v.1

Plan Number - CIP-0524-00017
Review Name: CIP - DEV SITE + COMM STRUCTURE - FINAL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
Commercial Plumbing APPROVED
Floodplain Administration Review APPROVED Tucson Water to provide periodic testing reports to Stormwater Management.
Bldg Permits - Post Review REQUIRES RESUBMIT Please address electrical comments on your next submittal.
Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 No written narrative or response found addressing the previous electrical review comments as requested.

2 Verify that all the main circuit breakers associated with this project comply with NEC art 240.87 and are equipped accordingly.

3 Ref; Plan sheet E15. Verify complete compliance with the 2012 City of Tucson Outdoor Lighting code for the exterior mounted ā€˜Dā€™ luminaires shown on this plan.

4 Provide complete compliance with the 2018 IECC for the lighting. Do not confuse the IECC requirements with the 2012 COT Outdoor Lighting Code.

Because of the nature of the review comments, additional comments may be generated at the subsequent review.

Ref; 2018 IBC section 107.2.1, 2017 NEC, 2012 City of Tucson Outdoor Lighting Code.
CDRC Application Completeness REVIEW COMPLETED
CDRC Post Review REVIEW COMPLETED DP Portion of this project has been completed. Please submit all documentation supporting external review approvals, required permits, and reports to your DP application using your TDC online applicant account. For further assistance please contact Aaron or Sonya at CDRC@tucsonaz.gov
Historic REVIEW COMPLETED This project is in an area that has already had a survey - so long as the work stays within the boundary of the previous work, it will not need an archeological monitor. Thank you. Questions. PDSDHistoric@tucsonaz.gov
PDSD Application Completeness REVIEW COMPLETED