Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Plan Review Detail
Review Status: Requires Resubmit
Review Details: CIP - DEV SITE + COMM STRUCTURE - FINAL v.2
Plan Number - CIP-0524-00017
Review Name: CIP - DEV SITE + COMM STRUCTURE - FINAL v.2
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
Bldg Permits - Post Review | REVIEW COMPLETED | Please address the electrical review comments with your next submittal. This cannot be moved into actual permitting until this review has been approved. If you have any questions about these comments, I can be reached at Matthew.Carlton@tucsonaz.gov |
|||
CDRC Post Review | REVIEW COMPLETED | Resubmittal is required for CIP Final Review due to lack of approvals. Next review must address all reviewer comments prior to allowing the completion of the CIP process. Please also fill out additional info screen for area of disturbance. If a dust permit is required please upload once complete. If you have questions please reach out to Sonya or Aaron at CDRC@tucsonaz.gov. | |||
Commercial Electrical | REVIEW COMPLETED | Please address the electrical plan review comments and provide a written response. 1 Thank you for the written response, however plans were not uploaded in Bluebeam for review. 2 Why were there 2 different Outdoor Lighting calculations submitted each having a different Parcel size? Ref; 2018 IBC section 107.2.1, 2017 NEC, 2012 City of Tucson Outdoor Lighting Code. |