Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Plan: T10FR00129
Plan Details
Apply Date:
01/21/2010
Applicant:
N/A
Description:
FIRE
Completed Inspections
Permit Status:
Permit Number:
Permit Description:
Total Completed Inspections - 1
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/21/2010 | INSP - FULL | RDUARTE | Approved | Petition of Appeal to the Fire Code Official for Bedand Breakfast over 2000 sq. ft required to use NFPA 13R Std. Explain why conformance with the above requirement presents an unusual problem- An extensive pump and tank system is already in place but is not specifically UL listed for fire protection as required by NFPA 13R standard. plus porch coverage not feasable due to historic nature of structure. STATE SPECIFICALLY WHAT IS PROPOSED IN LIEU OF LITERAL COMPLIANCE- Use of NFPA 13D Standard in lieu of NFPA13R, eliminate porch coverage. DECISION OF THE FIRE CODE OFFICIAL: Approved by Chief Dan Uthe Fire Marshal. 1/21/2010 |