Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Plan Number - T10FR00129
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/21/2010 | INSP - FULL | Approved | Petition of Appeal to the Fire Code Official for Bedand Breakfast over 2000 sq. ft required to use NFPA 13R Std. Explain why conformance with the above requirement presents an unusual problem- An extensive pump and tank system is already in place but is not specifically UL listed for fire protection as required by NFPA 13R standard. plus porch coverage not feasable due to historic nature of structure. STATE SPECIFICALLY WHAT IS PROPOSED IN LIEU OF LITERAL COMPLIANCE- Use of NFPA 13D Standard in lieu of NFPA13R, eliminate porch coverage. DECISION OF THE FIRE CODE OFFICIAL: Approved by Chief Dan Uthe Fire Marshal. 1/21/2010 |