Plan Details

Status:
Complete
Type:
FIREINSP
Apply Date:
09/02/2008
Applicant:
N/A
Description:
FIRE

Outstanding Inspections

Permit Status:
Permit Number:
Permite Description:
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
INSP - FULL Not Inspected

Completed Inspections

Permit Status:
Permit Number:
Permit Description:
Total Completed Inspections - 1
Date Description Inspector Results Comments
09/02/2008 VIOL - ADMINISTRATION RDUARTE Approved Petition of appeal to the Fire Chief- Sun Tran (BSMF) A vaulted system is not practical for this location due to the size & cost of such a system.

Approved- per Chief Dan Uthe, 09/02/08.

(State specifcally what is proposed in lieu of literal compliance)
Tanks shall have a maximum capacity of 18,000 gallons each, and shall be ballistic- resistant UL 2085 rated tanks. Up to four of these tanks shall be allowed. They must have a masonry screen wall on the road side that obstructs the view of the entire tank.