Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - ADMINISTRATION
Plan Number - T08FR02603
Inspection Description - VIOL - ADMINISTRATION
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/02/2008 | VIOL - ADMINISTRATION | Approved | Petition of appeal to the Fire Chief- Sun Tran (BSMF) A vaulted system is not practical for this location due to the size & cost of such a system. Approved- per Chief Dan Uthe, 09/02/08. (State specifcally what is proposed in lieu of literal compliance) Tanks shall have a maximum capacity of 18,000 gallons each, and shall be ballistic- resistant UL 2085 rated tanks. Up to four of these tanks shall be allowed. They must have a masonry screen wall on the road side that obstructs the view of the entire tank. |