Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: TF-FCP-0724-00604
Permit Details
Status:
Complete
Type:
Fire Construction Permit
Address:
820 E TUCSON MARKETPLACE BL
Address NEW:
820 E TUCSON MARKETPLACE BL
Apply Date:
07/25/2024
Applicant:
Tim Proskine
Description:
Install a new wet pipe fire sprinkler system on all 3 floors.
Permit Reviews
Permit Number - TF-FCP-0724-00604
Permit Status: Complete
Permit Description: Install a new wet pipe fire sprinkler system on all 3 floors.
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 08/27/2024 | FIRE CONSTRUCTION REVIEW v.3 | 09/03/2024 | APPROVED |
| 07/30/2024 | FIRE CONSTRUCTION REVIEW v.2 | 08/14/2024 | REQUIRES RESUBMIT |
| 07/30/2024 | FIRE CONSTRUCTION REVIEW v.1 | 07/30/2024 | REQUIRES RESUBMIT |
Outstanding Inspections
Permit Status: Complete
Permit Number: TF-FCP-0724-00604
Permite Description: Install a new wet pipe fire sprinkler system on all 3 floors.
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/25/2025 | FCON – OH Piping & Hydro | N/A | Partial Pass | 200 lb on moved branch lines on 3rd floor ok. |
| 01/13/2026 | COT - FCON - Sprinkler - Final | N/A | Re-inspection required (with fee) | Missing coverage in ceiling pockets on third floor (per approved plan). Head covers caulked to ceiling on fistr and second floor. heads covered in both stairwells on 1st floor. Ceiling shall be intact. |
Completed Inspections
Permit Status: Complete
Permit Number: TF-FCP-0724-00604
Permit Description: Install a new wet pipe fire sprinkler system on all 3 floors.
Total Completed Inspections - 2
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/13/2026 | FCON – OH Piping & Hydro | Passed | ||
| 01/16/2026 | COT - FCON - Sprinkler - Final | Passed |