Permit Details

Status:
Complete
Type:
Fire Construction Permit
Apply Date:
07/25/2024
Applicant:
Tim Proskine
Description:
Install a new wet pipe fire sprinkler system on all 3 floors.

Permit Reviews

Permit Number - TF-FCP-0724-00604
Permit Status: Complete
Permit Description: Install a new wet pipe fire sprinkler system on all 3 floors.
Start Date Submittal Complete Date Status  
08/27/2024 FIRE CONSTRUCTION REVIEW v.3 09/03/2024 APPROVED Review Details
07/30/2024 FIRE CONSTRUCTION REVIEW v.2 08/14/2024 REQUIRES RESUBMIT Review Details
07/30/2024 FIRE CONSTRUCTION REVIEW v.1 07/30/2024 REQUIRES RESUBMIT Review Details

Outstanding Inspections

Permit Status: Complete
Permit Number: TF-FCP-0724-00604
Permite Description: Install a new wet pipe fire sprinkler system on all 3 floors.
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
08/25/2025 FCON – OH Piping & Hydro N/A Partial Pass 200 lb on moved branch lines on 3rd floor ok.
01/13/2026 COT - FCON - Sprinkler - Final N/A Re-inspection required (with fee) Missing coverage in ceiling pockets on third floor (per approved plan). Head covers caulked to ceiling on fistr and second floor. heads covered in both stairwells on 1st floor. Ceiling shall be intact.

Completed Inspections

Permit Status: Complete
Permit Number: TF-FCP-0724-00604
Permit Description: Install a new wet pipe fire sprinkler system on all 3 floors.
Total Completed Inspections - 2
Date Description Inspector Results Comments
01/13/2026 FCON – OH Piping & Hydro Passed
01/16/2026 COT - FCON - Sprinkler - Final Passed