Permit: TF-FCP-0526-00336
Permit Details
Status:
In Review
Type:
Fire Construction Permit
Address:
1151 E HERMANS RD BLDG 807
Address NEW:
1151 E HERMANS RD BLDG 807
Apply Date:
05/19/2026
Applicant:
Bryan Kauffman
Description:
1. PROJECT DESCRIPTION THIS PROJECT CONSISTS OF RELOCATING ONE (1) EXISTING MANUAL PULL STATION ON AN EXISTING NOTIFIER FIRE ALARM SYSTEM. 2. EXISTING SYSTEM THE EXISTING NOTIFIER FIRE ALARM SYSTEM SHALL REMAIN IN SERVICE. THE EXISTING SIGNALING LINE CIRCUIT (SLC) SHALL REMAIN CLASS A. 3. INITIATING DEVICES RELOCATE ONE (1) EXISTING MANUAL PULL STATION AS INDICATED ON THE DRAWINGS. THE RELOCATED DEVICE SHALL REMAIN CONNECTED TO THE EXISTING CLASS A SIGNALING LINE CIRCUIT. 4. WIRING EXISTING WIRING SHALL BE REUSED WHERE FEASIBLE. NEW WIRING SHALL BE INSTALLED AS REQUIRED TO SUPPORT THE NEW DEVICE LOCATION. ALL NEW FIRE ALARM WIRING SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 70, NFPA 72, APPLICABLE LOCAL CODES, AND MANUFACTURER REQUIREMENTS. THE EXISTING CLASS A CIRCUIT CONFIGURATION SHALL BE MAINTAINED. 5. PROGRAMMING, TESTING, AND ACCEPTANCE MODIFY EXISTING SYSTEM PROGRAMMING AS REQUIRED. PERFORM FUNCTIONAL TESTING OF THE RELOCATED MANUAL PULL STATION TO VERIFY PROPER SYSTEM OPERATION. VERIFY PROPER OPERATION OF THE EXISTING CLASS A SIGNALING LINE CIRCUIT. 6. SCOPE LIMITATIONS WORK INCLUDED IN THIS SCOPE IS LIMITED TO THE FIRE ALARM SYSTEM COMPONENTS DESCRIBED HEREIN.
Permit Reviews
Permit Number - TF-FCP-0526-00336
Permit Status: In review
Permit Description: 1. PROJECT DESCRIPTION
THIS PROJECT CONSISTS OF RELOCATING ONE (1) EXISTING MANUAL PULL STATION ON AN EXISTING NOTIFIER FIRE ALARM SYSTEM.
2. EXISTING SYSTEM
THE EXISTING NOTIFIER FIRE ALARM SYSTEM SHALL REMAIN IN SERVICE.
THE EXISTING SIGNALING LINE CIRCUIT (SLC) SHALL REMAIN CLASS A.
3. INITIATING DEVICES
RELOCATE ONE (1) EXISTING MANUAL PULL STATION AS INDICATED ON THE DRAWINGS.
THE RELOCATED DEVICE SHALL REMAIN CONNECTED TO THE EXISTING CLASS A SIGNALING LINE CIRCUIT.
4. WIRING
EXISTING WIRING SHALL BE REUSED WHERE FEASIBLE.
NEW WIRING SHALL BE INSTALLED AS REQUIRED TO SUPPORT THE NEW DEVICE LOCATION.
ALL NEW FIRE ALARM WIRING SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 70, NFPA 72, APPLICABLE LOCAL CODES, AND
MANUFACTURER REQUIREMENTS.
THE EXISTING CLASS A CIRCUIT CONFIGURATION SHALL BE MAINTAINED.
5. PROGRAMMING, TESTING, AND ACCEPTANCE
MODIFY EXISTING SYSTEM PROGRAMMING AS REQUIRED.
PERFORM FUNCTIONAL TESTING OF THE RELOCATED MANUAL PULL STATION TO VERIFY PROPER SYSTEM OPERATION.
VERIFY PROPER OPERATION OF THE EXISTING CLASS A SIGNALING LINE CIRCUIT.
6. SCOPE LIMITATIONS
WORK INCLUDED IN THIS SCOPE IS LIMITED TO THE FIRE ALARM SYSTEM COMPONENTS DESCRIBED HEREIN.
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 05/19/2026 | FIRE CONSTRUCTION REVIEW v.1 | N/A | IN REVIEW |