Type:
Solar
Address NEW:
3461 W FOXES DEN DR
Apply Date:
11/09/2025
Applicant:
David Hosking
Description:
Rooftop Solar

Permit Reviews

Permit Number - TC-SOL-1125-01484
Permit Status: Inspections
Permit Description: Rooftop Solar
Start Date Submittal Complete Date Status  
11/10/2025 RESIDENTIAL SOLAR APP v.1 11/10/2025 APPROVED Review Details

Outstanding Inspections

Permit Status: Inspections
Permit Number: TC-SOL-1125-01484
Permite Description: Rooftop Solar
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
12/09/2025 BULD - Electrical Clearance N/A Partial Pass ESS is too far away from Disconnect and not within line of sight. See notes below:


A readily accessible disconnect shall be provided within sight of the ESS [NEC 706.7(A)]

Where remote actuation of the disconnecting means is employed the controls are not within sight of the ESS, the disconnecting means shall be capable of being locked in the open position. [NEC 706.7(B); 110.25]

Where ESS input and output terminals are more than 5ft from connected equipment, or where circuits from these terminals pass through a wall or partition;- A disconnecting means is required at the ESS end of the circuit- If this disconnect is not within sight of the connected equipment a second disconnecting means is required at the connected equipment. [NEC 706.7(E)(1); 706.7(E)(2)]

The disconnecting means for the ESS shall be legibly marked with the nominal ESS voltage, the maximum available fault current from the ESS and the associated clearing time, and the date the calculation was performed. [NEC 706.7
12/09/2025 COT - RSOL - Electrical Final Solar Project N/A Not Ready

Completed Inspections

Permit Status: Inspections
Permit Number: TC-SOL-1125-01484
Permit Description: Rooftop Solar
Total Completed Inspections - 2
Date Description Inspector Results Comments
01/07/2026 BULD - Electrical Clearance Passed 1.7.26
Cleared for DGC clearance
01/07/2026 COT - RSOL - Electrical Final Solar Project Passed 1.7.26
Approved