Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Parcel: 11627423A


Addresses:

3461 W FOXES DEN DR


Inspection Status: Passed

Inspection History: BULD - Electrical Clearance

Permit Number - TC-SOL-1125-01484

Inspection Description - BULD - Electrical Clearance

Inspection Status - Passed

Date Description Inspector Results Comments
01/07/2026 BULD - Electrical Clearance Passed 1.7.26
Cleared for DGC clearance
12/09/2025 BULD - Electrical Clearance Partial Pass ESS is too far away from Disconnect and not within line of sight. See notes below:


A readily accessible disconnect shall be provided within sight of the ESS [NEC 706.7(A)]

Where remote actuation of the disconnecting means is employed the controls are not within sight of the ESS, the disconnecting means shall be capable of being locked in the open position. [NEC 706.7(B); 110.25]

Where ESS input and output terminals are more than 5ft from connected equipment, or where circuits from these terminals pass through a wall or partition;- A disconnecting means is required at the ESS end of the circuit- If this disconnect is not within sight of the connected equipment a second disconnecting means is required at the connected equipment. [NEC 706.7(E)(1); 706.7(E)(2)]

The disconnecting means for the ESS shall be legibly marked with the nominal ESS voltage, the maximum available fault current from the ESS and the associated clearing time, and the date the calculation was performed. [NEC 706.7