Permit: TC-RES-1224-07168
Permit Details
Status:
Inspections
Type:
Residential Building - One or Two Family
Address:
3715 N STONE AV UNIT 2
Address NEW:
3715 N STONE AV UNIT 2
Apply Date:
12/10/2024
Applicant:
Jake Boen
Description:
Repair from Vehicle Damage
Permit Reviews
Permit Number - TC-RES-1224-07168
Permit Status: Inspections
Permit Description: Repair from Vehicle Damage
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 12/11/2024 | RESIDENTIAL NEW DWELLING v.1 | 01/13/2025 | REQUIRES RESUBMIT |
| 09/12/2025 | RESIDENTIAL NEW DWELLING v.3 | 10/02/2025 | APPROVED |
| 11/25/2025 | BUILDING DEFERRED SUBMITTAL REVIEW v.2 | 11/26/2025 | APPROVED |
| 06/18/2025 | RESIDENTIAL NEW DWELLING v.2 | 07/02/2025 | REQUIRES RESUBMIT |
| 11/10/2025 | BUILDING DEFERRED SUBMITTAL REVIEW v.1 | 11/14/2025 | REQUIRES RESUBMIT |
Conditions
Permit Number - TC-RES-1224-07168
Permit Status: Inspections
Permit Description: Repair from Vehicle Damage
| Date | Description | Comments |
|---|---|---|
| 12/11/2024 | Contractor with active Arizona Contractor's License for specified scope of work, or a signed Owner Builder Affidavit https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/residential-permits/pdsd_owner_builder_affidavit_081623.pdf, is required prior to issuance of permit. Contractor or Owner must have a TDC Online account and be added to the permit as the correct contact type https://www.tucsonaz.gov/files/sharedassets/public/v/2/pdsd/documents/tdc-faq/new-pdfs/adding-additional-contacts.pdf. If you are providing an Owner Builder Affidavit, the owner MUST be attached as a contact on the permit. | |
| 11/13/2025 | SPECIAL INSPECTION FOR EPOXY ANCHORS IS REQUIRED. |
Outstanding Inspections
Permit Status: Inspections
Permit Number: TC-RES-1224-07168
Permite Description: Repair from Vehicle Damage
Total Outstanding Inspections - 5
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/12/2025 | COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. | N/A | Not Ready | Please protect gas line in Masonary wall with 10 mil tape |
| 02/11/2026 | COT - RSME - Mechanical Final | N/A | Re-inspection required | 2/11/2026 Outdoor light at entrance not operating, furnace missing, refrigerator in living room, air registers are covered. Hot water heater outside verified not in scope of work: not connected, flue cap broken, gas line missing drip leg, T&P valve not piped. Dead front at main service panel needs labeled complete, knockouts need plugged at bottom. Missing smoke detector in bedroom and hall, missing outlets in bedroom & living room, outside receptacles need to be outdoor rated, and arc fault breakers needed in habitable areas. |
| 02/11/2026 | RSBU - Building Final | N/A | Re-inspection required | 2/11/2026 Outdoor light at entrance not operating, furnace missing, refrigerator in living room, air registers are covered. Hot water heater outside verified not in scope of work: not connected, flue cap broken, gas line missing drip leg, T&P valve not piped. Dead front at main service panel needs labeled complete, knockouts need plugged at bottom. Missing smoke detector in bedroom and hall, missing outlets in bedroom & living room, outside receptacles need to be outdoor rated, and arc fault breakers needed in habitable areas. |
| 02/11/2026 | COT - RSPL - Plumbing Final | N/A | Re-inspection required | 2/11/2026 Outdoor light at entrance not operating, furnace missing, refrigerator in living room, air registers are covered. Hot water heater outside verified not in scope of work: not connected, flue cap broken, gas line missing drip leg, T&P valve not piped. Dead front at main service panel needs labeled complete, knockouts need plugged at bottom. Missing smoke detector in bedroom and hall, missing outlets in bedroom & living room, outside receptacles need to be outdoor rated, and arc fault breakers needed in habitable areas. |
| 02/11/2026 | COT - RSEL - Electrical Final | N/A | Re-inspection required | 2/11/2026 Outdoor light at entrance not operating, furnace missing, refrigerator in living room, air registers are covered. Hot water heater outside verified not in scope of work: not connected, flue cap broken, gas line missing drip leg, T&P valve not piped. Dead front at main service panel needs labeled complete, knockouts need plugged at bottom. Missing smoke detector in bedroom and hall, missing outlets in bedroom & living room, outside receptacles need to be outdoor rated, and arc fault breakers needed in habitable areas. |
Completed Inspections
Permit Status: Inspections
Permit Number: TC-RES-1224-07168
Permit Description: Repair from Vehicle Damage
Total Completed Inspections - 7
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/24/2025 | COT - RSBU - Masonry Pregrout | Passed | ||
| 01/15/2026 | COT - RSBU - Firewall/Fire Barrier/Firestop | Passed | ||
| 01/27/2026 | COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. | Passed | ||
| 04/30/2026 | COT - RSME - Mechanical Final | Passed | ||
| 04/30/2026 | COT - RSPL - Plumbing Final | Passed | ||
| 04/30/2026 | COT - BULD - SWG Clearance | Passed | SWG | |
| 04/30/2026 | COT - RSEL - Electrical Final | Passed |