Permit Details

Status:
Issued
Type:
Residential Building - One or Two Family
Address:
7611 E 42ND ST
Address NEW:
7611 E 42ND ST
Apply Date:
11/22/2023
Applicant:
Jabril Thomas
Description:
Move gas meter to side of utility room (performed by SWG Coyl program). Run 60ft of gas pipe, 48 is one inch, 8 is 3/4 inch and 4 is half inch. 40 ft of 1 inch pipe spanned across roof of structure to new meter location to avoid moving current gas line in ground. Revision 1: Include the update or replacement of the electrical panel. Replacement of all electrical outlets.

Permit Reviews

Permit Number - TC-RES-1123-09675
Permit Status: Issued
Permit Description: Move gas meter to side of utility room (performed by SWG Coyl program). Run 60ft of gas pipe, 48 is one inch, 8 is 3/4 inch and 4 is half inch. 40 ft of 1 inch pipe spanned across roof of structure to new meter location to avoid moving current gas line in ground. Revision 1: Include the update or replacement of the electrical panel. Replacement of all electrical outlets.
Start Date Submittal Complete Date Status  
12/08/2023 RESIDENTIAL SIMPLE REVIEW v.1 12/08/2023 REQUIRES RESUBMIT Review Details
12/11/2023 RESIDENTIAL SIMPLE REVIEW v.2 12/12/2023 APPROVED Review Details
11/22/2023 RESIDENTIAL SIMPLE REVIEW v.1 11/22/2023 APPROVED Review Details

Conditions

Permit Number - TC-RES-1123-09675
Permit Status: Issued
Permit Description: Move gas meter to side of utility room (performed by SWG Coyl program). Run 60ft of gas pipe, 48 is one inch, 8 is 3/4 inch and 4 is half inch. 40 ft of 1 inch pipe spanned across roof of structure to new meter location to avoid moving current gas line in ground. Revision 1: Include the update or replacement of the electrical panel. Replacement of all electrical outlets.
Date Description Comments
11/22/2023 Contractor with active Arizona Contractor's License for specified scope of work, or a signed Owner Builder Affidavit https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/residential-permits/pdsd_owner_builder_affidavit_081623.pdf, is required prior to issuance of permit. Contractor or Owner must have a TDC Online account and be added to the permit as a contact. If you are providing an Owner Builder Affidavit, the owner MUST be attached as a contact on the permit.

Outstanding Inspections

Permit Status: Issued
Permit Number: TC-RES-1123-09675
Permite Description: Move gas meter to side of utility room (performed by SWG Coyl program). Run 60ft of gas pipe, 48 is one inch, 8 is 3/4 inch and 4 is half inch. 40 ft of 1 inch pipe spanned across roof of structure to new meter location to avoid moving current gas line in ground. Revision 1: Include the update or replacement of the electrical panel. Replacement of all electrical outlets.
Total Outstanding Inspections - 3
Last Inspection Date Description Inspector Results Comments
12/13/2023 BULD - Electrical Clearance N/A Re-inspection required 1-Install address label. 2-Grounding Electrode Conductor needs to be irreversibly connected; split bolt is not allowed. 3-Panel had no main breaker; violates the six movements of the hand requirement in the NEC.
12/13/2023 RSEL - Electrical Progress N/A Re-inspection required 1-Install address label. 2-Grounding Electrode Conductor needs to be irreversibly connected; split bolt is not allowed. 3-Panel had no main breaker; violates the six movements of the hand requirement in the NEC.
12/13/2023 COT - RSEL - Electrical Final N/A Re-inspection required 1-Install address label. 2-Grounding Electrode Conductor needs to be irreversibly connected; split bolt is not allowed. 3-Panel had no main breaker; violates the six movements of the hand requirement in the NEC.4-Label panel.

Completed Inspections

Permit Status: Issued
Permit Number: TC-RES-1123-09675
Permit Description: Move gas meter to side of utility room (performed by SWG Coyl program). Run 60ft of gas pipe, 48 is one inch, 8 is 3/4 inch and 4 is half inch. 40 ft of 1 inch pipe spanned across roof of structure to new meter location to avoid moving current gas line in ground. Revision 1: Include the update or replacement of the electrical panel. Replacement of all electrical outlets.
Total Completed Inspections - 5
Date Description Inspector Results Comments
11/29/2023 COT - BULD - SWG Clearance Passed Gas piping is installed from new meter location to the furnace closet for the gas water heater and furnace. Contractor for Southwest Gas is onsite trenching for new gas line from alley to new meter location. Okay to turn on gas once installation is complete of gas line from main supply line.
11/29/2023 COT - RSPL - Plumbing Final Passed Gas piping is installed from new meter location to the furnace closet for the gas water heater and furnace. Contractor for Southwest Gas is onsite trenching for new gas line from alley to new meter location. Okay to turn on gas once installation is complete of gas line from main supply line.
04/19/2024 BULD - Electrical Clearance Passed Electrical grounding has been corrected, address label has been installed, 200 amp main disconnect breaker has been installed in main panel. TEP has energize system so no clearance is required.
04/19/2024 RSEL - Electrical Progress Passed Electrical grounding has been corrected, address label has been installed, 200 amp main disconnect breaker has been installed in main panel. TEP has energize system so no clearance is required.
04/19/2024 COT - RSEL - Electrical Final Passed Electrical grounding has been corrected, address label has been installed, 200 amp main disconnect breaker has been installed in main panel. TEP has energize system so no clearance is required.

Documents

File Name Document Type  
7611 E 42ND - PDSD_OWNER_BUILDER_AFFIDAVIT_081623 - COMPLETED REVISED_V1.PDF DOCUMENTS VIEW
COFT - PDSD - PERMIT CARD.PDF DOCUMENTS VIEW
PHOTOS 7611 E 42ND_V1.PDF DOCUMENTS VIEW
PLANS 7611 E 42ND_V1.PDF DOCUMENTS VIEW