Inspection Status: Passed
Inspection History: BULD - Electrical Clearance
| Date |
Description |
Inspector |
Results |
Comments |
| 04/19/2024 |
BULD - Electrical Clearance |
|
Passed |
Electrical grounding has been corrected, address label has been installed, 200 amp main disconnect breaker has been installed in main panel. TEP has energize system so no clearance is required. |
| 12/13/2023 |
BULD - Electrical Clearance |
|
Re-inspection required |
1-Install address label. 2-Grounding Electrode Conductor needs to be irreversibly connected; split bolt is not allowed. 3-Panel had no main breaker; violates the six movements of the hand requirement in the NEC. |