Permit: TC-RES-1123-09675

Parcel: 136340690


Addresses:

7611 E 42ND ST

Inspection Status: Passed

Inspection History: BULD - Electrical Clearance

Date Description Inspector Results Comments
04/19/2024 BULD - Electrical Clearance Passed Electrical grounding has been corrected, address label has been installed, 200 amp main disconnect breaker has been installed in main panel. TEP has energize system so no clearance is required.
12/13/2023 BULD - Electrical Clearance Re-inspection required 1-Install address label. 2-Grounding Electrode Conductor needs to be irreversibly connected; split bolt is not allowed. 3-Panel had no main breaker; violates the six movements of the hand requirement in the NEC.