Permit Details

Status:
Complete
Type:
Residential Building - One or Two Family
Address NEW:
1015 W COLORADO ST
Apply Date:
09/24/2025
Applicant:
Analy Guzman
Description:
(Work done without a permit.) Alterations of existing structures, 1. converting the attached carport to livable space. 196sf 2. Converting the attached storage shed to a livable space. 86sf

Permit Reviews

Permit Number - TC-RES-0925-04710
Permit Status: Complete
Permit Description: (Work done without a permit.) Alterations of existing structures, 1. converting the attached carport to livable space. 196sf 2. Converting the attached storage shed to a livable space. 86sf
Start Date Submittal Complete Date Status  
09/29/2025 RESIDENTIAL ADD/ALT v.1 10/30/2025 REQUIRES RESUBMIT Review Details
12/19/2025 ADMINISTRATIVE v.1 12/19/2025 REQUIRES RESUBMIT Review Details
12/01/2025 RESIDENTIAL ADD/ALT v.2 12/19/2025 APPROVED Review Details
12/31/2025 ADMINISTRATIVE v.3 12/31/2025 APPROVED Review Details
12/30/2025 ADMINISTRATIVE v.2 12/30/2025 REQUIRES RESUBMIT Review Details

Conditions

Permit Number - TC-RES-0925-04710
Permit Status: Complete
Permit Description: (Work done without a permit.) Alterations of existing structures, 1. converting the attached carport to livable space. 196sf 2. Converting the attached storage shed to a livable space. 86sf
Date Description Comments
09/29/2025 Contractor with active Arizona Contractor's License for specified scope of work, or a signed Owner Builder Affidavit is required prior to issuance of permit. The Affidavit form is available at https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Residential-Permits. Contractor or Owner must have a TDC Online account and be added to the permit as the correct contact type https://www.tucsonaz.gov/files/sharedassets/public/v/2/pdsd/documents/tdc-faq/new-pdfs/adding-additional-contacts.pdf. If you are providing an Owner Builder Affidavit, the owner MUST be attached as a contact on the permit.

Outstanding Inspections

Permit Status: Complete
Permit Number: TC-RES-0925-04710
Permite Description: (Work done without a permit.) Alterations of existing structures, 1. converting the attached carport to livable space. 196sf 2. Converting the attached storage shed to a livable space. 86sf
Total Outstanding Inspections - 5
Last Inspection Date Description Inspector Results Comments
01/15/2026 RSBU - Building Final N/A Re-inspection required Inspection Date: 01/15/2026
Status: STOPPED INSPECTION – Additional items may be added
Hot and neutral reversed at the bathroom receptacle in the north bedroom, Hot and neutral reversed at the north bedroom receptacle, Receptacle spacing throughout the dwelling does not comply with NEC requirements, Bathroom receptacle at the south unit must be GFCI protected, All exterior receptacles must be GFCI protected and WR-rated.
Sub-panel could not be located at the time of inspection, Kitchen receptacle spacing must comply with NEC requirements and be GFCI protected, Receptacle located beneath the kitchen sink must be GFCI protected and provided with an appropriate cover, All exterior junction boxes must be rated for exterior use and provided with approved exterior-rated covers, Existing home has been re-wired and re-plumbed; a revision to the permit is required, Water heater was replaced without an approved permit, HVAC system was replaced without an approved permit, All mini-split systems installed are from Mexico; documentation from a third-party testing agency is required to verify compliance with UL listing requirements for equipment installed in the United States, Refrigerant lines for mini-split systems must be UV protected, Covered framing members must be exposed for inspection to verify code compliance, Laundry room framing is not code compliant and must be corrected, Water closet clearance requirements are not met at the north bedroom bathroom, Piping used at the north bedroom bathroom lavatory is not code compliant, Piping beneath the kitchen sink must be properly connected to ensure appropriate discharge, Exterior plastic piping must be properly supported and protected from UV exposure, DWV system must be tested for leaks, and proper burial depth must be verified, Laundry room window must be replaced with tempered glass, as it is located within 24 inches of the door,All entrances must comply with the City of Tucson all-inclusive ordinances.
01/15/2026 RSBU - Building Progress N/A Not Ready
01/15/2026 COT - RSME - Mechanical Final N/A Re-inspection required Inspection Date: 01/15/2026
Status: STOPPED INSPECTION – Additional items may be added
Hot and neutral reversed at the bathroom receptacle in the north bedroom, Hot and neutral reversed at the north bedroom receptacle, Receptacle spacing throughout the dwelling does not comply with NEC requirements, Bathroom receptacle at the south unit must be GFCI protected, All exterior receptacles must be GFCI protected and WR-rated.
Sub-panel could not be located at the time of inspection, Kitchen receptacle spacing must comply with NEC requirements and be GFCI protected, Receptacle located beneath the kitchen sink must be GFCI protected and provided with an appropriate cover, All exterior junction boxes must be rated for exterior use and provided with approved exterior-rated covers, Existing home has been re-wired and re-plumbed; a revision to the permit is required, Water heater was replaced without an approved permit, HVAC system was replaced without an approved permit, All mini-split systems installed are from Mexico; documentation from a third-party testing agency is required to verify compliance with UL listing requirements for equipment installed in the United States, Refrigerant lines for mini-split systems must be UV protected, Covered framing members must be exposed for inspection to verify code compliance, Laundry room framing is not code compliant and must be corrected, Water closet clearance requirements are not met at the north bedroom bathroom, Piping used at the north bedroom bathroom lavatory is not code compliant, Piping beneath the kitchen sink must be properly connected to ensure appropriate discharge, Exterior plastic piping must be properly supported and protected from UV exposure, DWV system must be tested for leaks, and proper burial depth must be verified, Laundry room window must be replaced with tempered glass, as it is located within 24 inches of the door,All entrances must comply with the City of Tucson all-inclusive ordinances.
01/15/2026 COT - RSPL - Plumbing Final N/A Re-inspection required Inspection Date: 01/15/2026
Status: STOPPED INSPECTION – Additional items may be added
Hot and neutral reversed at the bathroom receptacle in the north bedroom, Hot and neutral reversed at the north bedroom receptacle, Receptacle spacing throughout the dwelling does not comply with NEC requirements, Bathroom receptacle at the south unit must be GFCI protected, All exterior receptacles must be GFCI protected and WR-rated.
Sub-panel could not be located at the time of inspection, Kitchen receptacle spacing must comply with NEC requirements and be GFCI protected, Receptacle located beneath the kitchen sink must be GFCI protected and provided with an appropriate cover, All exterior junction boxes must be rated for exterior use and provided with approved exterior-rated covers, Existing home has been re-wired and re-plumbed; a revision to the permit is required, Water heater was replaced without an approved permit, HVAC system was replaced without an approved permit, All mini-split systems installed are from Mexico; documentation from a third-party testing agency is required to verify compliance with UL listing requirements for equipment installed in the United States, Refrigerant lines for mini-split systems must be UV protected, Covered framing members must be exposed for inspection to verify code compliance, Laundry room framing is not code compliant and must be corrected, Water closet clearance requirements are not met at the north bedroom bathroom, Piping used at the north bedroom bathroom lavatory is not code compliant, Piping beneath the kitchen sink must be properly connected to ensure appropriate discharge, Exterior plastic piping must be properly supported and protected from UV exposure, DWV system must be tested for leaks, and proper burial depth must be verified, Laundry room window must be replaced with tempered glass, as it is located within 24 inches of the door,All entrances must comply with the City of Tucson all-inclusive ordinances.
01/15/2026 COT - RSEL - Electrical Final N/A Re-inspection required Inspection Date: 01/15/2026
Status: STOPPED INSPECTION – Additional items may be added
Hot and neutral reversed at the bathroom receptacle in the north bedroom, Hot and neutral reversed at the north bedroom receptacle, Receptacle spacing throughout the dwelling does not comply with NEC requirements, Bathroom receptacle at the south unit must be GFCI protected, All exterior receptacles must be GFCI protected and WR-rated.
Sub-panel could not be located at the time of inspection, Kitchen receptacle spacing must comply with NEC requirements and be GFCI protected, Receptacle located beneath the kitchen sink must be GFCI protected and provided with an appropriate cover, All exterior junction boxes must be rated for exterior use and provided with approved exterior-rated covers, Existing home has been re-wired and re-plumbed; a revision to the permit is required, Water heater was replaced without an approved permit, HVAC system was replaced without an approved permit, All mini-split systems installed are from Mexico; documentation from a third-party testing agency is required to verify compliance with UL listing requirements for equipment installed in the United States, Refrigerant lines for mini-split systems must be UV protected, Covered framing members must be exposed for inspection to verify code compliance, Laundry room framing is not code compliant and must be corrected, Water closet clearance requirements are not met at the north bedroom bathroom, Piping used at the north bedroom bathroom lavatory is not code compliant, Piping beneath the kitchen sink must be properly connected to ensure appropriate discharge, Exterior plastic piping must be properly supported and protected from UV exposure, DWV system must be tested for leaks, and proper burial depth must be verified, Laundry room window must be replaced with tempered glass, as it is located within 24 inches of the door,All entrances must comply with the City of Tucson all-inclusive ordinances.

Completed Inspections

Permit Status: Complete
Permit Number: TC-RES-0925-04710
Permit Description: (Work done without a permit.) Alterations of existing structures, 1. converting the attached carport to livable space. 196sf 2. Converting the attached storage shed to a livable space. 86sf
Total Completed Inspections - 4
Date Description Inspector Results Comments
07/02/2026 RSBU - Building Final Passed
07/02/2026 COT - RSME - Mechanical Final Passed
07/02/2026 COT - RSPL - Plumbing Final Passed
07/07/2026 COT - RSEL - Electrical Final Passed

Documents

File Name Document Type  
LOFC_LETTEROFCOMPLETION (SSRS).PDF DOCUMENTS VIEW
COFT - PDSD - PERMIT CARD (SSRS).PDF DOCUMENTS VIEW
2025-12-30 15-38_V2.PDF DOCUMENTS VIEW
COLORADO COMMENT RESPONSE LETTER_V1.PDF DOCUMENTS VIEW
CONS-1015 W COLORADO ST REV_V2.PDF DOCUMENTS VIEW