Permit: TC-RES-0923-07946
Permit Details
Status:
Issued
Type:
Residential Building - One or Two Family
Address:
6780 E 3RD ST
Address NEW:
6780 E 3RD ST
Apply Date:
09/12/2023
Applicant:
Rick D'Alessio
Description:
ADU
Permit Reviews
Permit Number - TC-RES-0923-07946
Permit Status: Issued
Permit Description: ADU
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 09/12/2023 | RESIDENTIAL NEW DWELLING v.1 | 10/06/2023 | REQUIRES RESUBMIT |
| 10/11/2023 | RESIDENTIAL NEW DWELLING v.2 | 10/27/2023 | APPROVED |
| 03/18/2024 | BUILDING DEFERRED SUBMITTAL REVIEW v.1 | 03/20/2024 | REQUIRES RESUBMIT |
| 04/05/2024 | BUILDING DEFERRED SUBMITTAL REVIEW v.2 | 04/08/2024 | APPROVED |
Outstanding Activity Conditions
Permit Number - TC-RES-0923-07946
Permit Status: Issued
Permit Description: ADU
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 01/18/2024 | Submit the Air Leakage & Duct Tightness Test Report completed by an Approved Special Inspector prior to Final Inspections. |
Conditions
Permit Number - TC-RES-0923-07946
Permit Status: Issued
Permit Description: ADU
| Date | Description | Comments |
|---|---|---|
| 10/16/2023 | Please contact Pima County Addressing to resolve issue. Addressing@pima.gov or 520-724-9512 | |
| 09/12/2023 | Contractor with active Arizona Contractor's License for specified scope of work, or a signed Owner Builder Affidavit https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/permits/residential-permits/pdsd_owner_builder_affidavit.pdf, is required prior to issuance of permit. Contractor or Owner must have a TDC Online account and be added to the permit as a contact. If you are providing an Owner Builder Affidavit, the owner MUST be attached as a contact on the permit. | |
| 03/20/2024 | MANUAL J - Designs must be submitted and approved prior to Intermediate Inspection. Please submit a Manual J that uses one of the approved software in generating the document. Please touch base with your HVAC supplier/installer, they would have the proprietary software or know of someone who has it. This document should include the Manual J, D, S and Extended Rating Table information. | |
| 09/12/2023 | Separate submittal to PC RWRD is required for new connections to sewer, new water meters and upsized water meters. Contact sewer@pima.gov for review and assessment. |
Outstanding Inspections
Permit Status: Issued
Permit Number: TC-RES-0923-07946
Permite Description: ADU
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/27/2024 | COT - RSEL - Electrical Underground | N/A | Partial Pass | 2/27/24: electrical underground complete. Ground rods need to be installed correctly. E3608.1.4.1 Installation. The rod and pipe electrodes shall be installed such that at least 8 feet (2438 mm) of length is in contact with the soil. They shall be driven to a depth of not less than 8 feet (2438 mm) except that, where rock bottom is encountered, electrodes shall be driven at an oblique angle not to exceed 45 degrees (0.79 rad) from the vertical or shall be buried in a trench that is at least 30 inches (762 mm) deep. The upper end of the electrodes shall be flush with or below ground level except where the above-ground end and the grounding electrode conductor attachment are protected against physical damage. (250.53(G)] |
Completed Inspections
Permit Status: Issued
Permit Number: TC-RES-0923-07946
Permit Description: ADU
Total Completed Inspections - 16
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/29/2023 | COT - RSBU - Excavation/Rebar/Zoning | Passed | ||
| 12/20/2023 | COT - RSBU - Masonry Pregrout | Passed | Stem wall CMU block is properly laid, rebar reinforcement is 32" on center within the block cells. Okay to proceed with grout. | |
| 12/20/2023 | COT - RSPL - Rough Soil | Passed | Underground plumbing is connected to main sewer line and under a water test with no leaks. Okay to shade pipe, backfill trench, and proceed with compaction of sub-soil for slab on grade. | |
| 12/20/2023 | COT - RSPL - Sewer | Passed | Underground plumbing is connected to main sewer line and under a water test with no leaks. Okay to shade pipe, backfill trench, and proceed with compaction of sub-soil for slab on grade. | |
| 01/11/2024 | COT - RSBU - Preslab | Passed | ||
| 02/02/2024 | COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. | Passed | ||
| 02/21/2024 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Passed | ||
| 02/21/2024 | COT - RSBU - Roof Nailing | Passed | ||
| 03/01/2024 | BULD - Electrical Clearance | Passed | Conduit is ran from panel to transformer underground. Ground rod is properly installed and ground wire connected from ground bus bar to ground rod. ECO Clearance issued for TEP to energize system. | |
| 03/01/2024 | COT - RSEL - Electrical Underground | Passed | 3/1/24: Grounding rod has been driven to below grade. Okay to issue electrical clearance. | |
| 03/01/2024 | COT - RSEL - Grounding/Bonding | Passed | 3/1/24: Grounding rod has been driven to below grade. Okay to issue electrical clearance. | |
| 03/01/2024 | COT - RSPL - Yard Water Line | Passed | Water line is connected to the meter and a blue tracer wire is attached from meter to exterior hose bib. Okay to shade pipe and backfill trench. | |
| 06/03/2024 | RSBU - Building Final | Passed | ||
| 06/03/2024 | COT - RSEL - Electrical Final | Passed | ||
| 06/03/2024 | COT - RSME - Mechanical Final | Passed | ||
| 06/03/2024 | COT - RSPL - Plumbing Final | Passed |