Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Issued
Type:
Residential Building - One or Two Family
Address NEW:
6733 S DOWNING AV
Apply Date:
07/10/2023
Applicant:
Lewis Urling
Description:
Electricity was off for some time advised by TEP need permit for reconnection/inspection

Permit Reviews

Permit Number - TC-RES-0723-06416
Permit Status: Issued
Permit Description: Electricity was off for some time advised by TEP need permit for reconnection/inspection
Start Date Submittal Complete Date Status  
07/11/2023 RESIDENTIAL SIMPLE REVIEW v.1 07/11/2023 APPROVED Review Details

Outstanding Inspections

Permit Status: Issued
Permit Number: TC-RES-0723-06416
Permite Description: Electricity was off for some time advised by TEP need permit for reconnection/inspection
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
07/12/2023 BULD - Electrical Clearance N/A Not Ready Not ready. Electrical wires exposed to weather need to be replaced and in conduit. Wires in panel need to be landed. Add cover plates to knock out. Water and gas lines need to be bonded. Provide torque specs on torque lugs along with witness marks. 7/12/2023

Completed Inspections

Permit Status: Issued
Permit Number: TC-RES-0723-06416
Permit Description: Electricity was off for some time advised by TEP need permit for reconnection/inspection
Total Completed Inspections - 2
Date Description Inspector Results Comments
07/18/2023 COT - RSEL - Electrical Final Passed Approved - RECN Clearance to TEP is required for the reconnection (meter #154635663)
07/17/2023 BULD - Electrical Clearance Passed RECN Clearance to TEP is required for the reconnection (meter #154635663)

Documents

File Name Document Type  
COFT - PDSD - PERMIT CARD.PDF DOCUMENTS VIEW