Permit Details

Status:
Inspections
Type:
Residential Building - One or Two Family
Address NEW:
2142 W WAGON WHEELS DR
Apply Date:
06/01/2026
Applicant:
Kailey John
Description:
TEP Required Corrections (1) Riser is 1.25" Rigid. Minimum riser size needs to be 2" rigid/IMC. (See SR-305 note 5) (2) Rigid bracing attached to riser does not meet minimum requirements of SR-305, note 1 and Detail A. (3) Centerline of meter is too high, at 80". Must be a maximum of 6'3" to centerline. (See SR-305, note 12 and SR-405, note 4) (4) Address label must be screwed or riveted onto meter base. (5) Meter enclosure must be sealed with an access plate, not a basic KO seal (See SR-405 note 7)

Permit Reviews

Permit Number - TC-RES-0626-02865
Permit Status: Inspections
Permit Description: TEP Required Corrections (1) Riser is 1.25" Rigid. Minimum riser size needs to be 2" rigid/IMC. (See SR-305 note 5) (2) Rigid bracing attached to riser does not meet minimum requirements of SR-305, note 1 and Detail A. (3) Centerline of meter is too high, at 80". Must be a maximum of 6'3" to centerline. (See SR-305, note 12 and SR-405, note 4) (4) Address label must be screwed or riveted onto meter base. (5) Meter enclosure must be sealed with an access plate, not a basic KO seal (See SR-405 note 7)
Start Date Submittal Complete Date Status  
06/01/2026 RESIDENTIAL SIMPLE REVIEW v.1 06/01/2026 APPROVED Review Details

Conditions

Permit Number - TC-RES-0626-02865
Permit Status: Inspections
Permit Description: TEP Required Corrections (1) Riser is 1.25" Rigid. Minimum riser size needs to be 2" rigid/IMC. (See SR-305 note 5) (2) Rigid bracing attached to riser does not meet minimum requirements of SR-305, note 1 and Detail A. (3) Centerline of meter is too high, at 80". Must be a maximum of 6'3" to centerline. (See SR-305, note 12 and SR-405, note 4) (4) Address label must be screwed or riveted onto meter base. (5) Meter enclosure must be sealed with an access plate, not a basic KO seal (See SR-405 note 7)
Date Description Comments
06/01/2026 Contractor with active Arizona Contractor's License for specified scope of work, or a signed Owner Builder Affidavit is required prior to issuance of permit. The Affidavit form is available at https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Residential-Permits. Contractor or Owner must have a TDC Online account and be added to the permit as the correct contact type https://www.tucsonaz.gov/files/sharedassets/public/v/2/pdsd/documents/tdc-faq/new-pdfs/adding-additional-contacts.pdf. If you are providing an Owner Builder Affidavit, the owner MUST be attached as a contact on the permit.

Completed Inspections

Permit Status: Inspections
Permit Number: TC-RES-0626-02865
Permit Description: TEP Required Corrections (1) Riser is 1.25" Rigid. Minimum riser size needs to be 2" rigid/IMC. (See SR-305 note 5) (2) Rigid bracing attached to riser does not meet minimum requirements of SR-305, note 1 and Detail A. (3) Centerline of meter is too high, at 80". Must be a maximum of 6'3" to centerline. (See SR-305, note 12 and SR-405, note 4) (4) Address label must be screwed or riveted onto meter base. (5) Meter enclosure must be sealed with an access plate, not a basic KO seal (See SR-405 note 7)
Total Completed Inspections - 2
Date Description Inspector Results Comments
06/11/2026 BULD - Electrical Clearance Passed 06/11/2026
Clearance TEP INCR for panel replacement at 12:45pm.
06/11/2026 COT - RSEL - Electrical Final Passed 06/11/2026
Verified all branch circuits landed and labeled at dead front, SPD installed.