Permit: TC-RES-0325-01187
Permit Details
Status:
Complete
Type:
Residential Building - One or Two Family
Address:
6934 E RUTGERS PL
Address NEW:
6934 E RUTGERS PL
Apply Date:
03/05/2025
Applicant:
Collin Cardwell
Description:
Solar PV 4.05kw Roof Install
Permit Reviews
Permit Number - TC-RES-0325-01187
Permit Status: Complete
Permit Description: Solar PV 4.05kw Roof Install
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 03/05/2025 | RESIDENTIAL SOLAR v.1 | 04/02/2025 | APPROVED |
Completed Inspections
Permit Status: Complete
Permit Number: TC-RES-0325-01187
Permit Description: Solar PV 4.05kw Roof Install
Total Completed Inspections - 2
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/03/2025 | COT - RSOL - Electrical Final Solar Project | Passed | 7.3.25 DGC/BAT. PV system is installed as per plans. Proper conductors verified throughout. Proper breakers verified. Panel schedule is present. Address label present. Meter number recorded. Labeling present on all equipment and conduits. Equipment is properly secured. Proper grounding and bonding verified. DGC/BAT CLEARANCE TO TEP. |
|
| 07/03/2025 | BULD - Electrical Clearance | Passed | 7.3.25 DGC/BAT. PV system is installed as per plans. Proper conductors verified throughout. Proper breakers verified. Panel schedule is present. Address label present. Meter number recorded. Labeling present on all equipment and conduits. Equipment is properly secured. Proper grounding and bonding verified. DGC/BAT CLEARANCE TO TEP. |