Permit Details

Status:
Inspections
Type:
Residential Building - One or Two Family
Address:
4114 S 13TH AV
Address NEW:
4114 S 13TH AV
Apply Date:
02/28/2025
Applicant:
Kenneth Tanaka
Description:
Home owner had seen smoke in kitchen area and called fire department. Fire department Had used thermal imaging and found three hot spots in ceiling. After removing ceiling and located the old metal clad cable that was overheated and causing smoke, they called TEP to pull meter to de-energize panel. After meeting with insurance inspector was able to pin point the two electric runs that had to be replaced. All was safely removed and replace with new Romex 12/2 wire per NEC code.

Permit Reviews

Permit Number - TC-RES-0225-01111
Permit Status: Inspections
Permit Description: Home owner had seen smoke in kitchen area and called fire department. Fire department Had used thermal imaging and found three hot spots in ceiling. After removing ceiling and located the old metal clad cable that was overheated and causing smoke, they called TEP to pull meter to de-energize panel. After meeting with insurance inspector was able to pin point the two electric runs that had to be replaced. All was safely removed and replace with new Romex 12/2 wire per NEC code.
Start Date Submittal Complete Date Status  
03/05/2025 RESIDENTIAL NEW DWELLING v.1 03/06/2025 REQUIRES RESUBMIT Review Details
03/06/2025 RESIDENTIAL NEW DWELLING v.2 03/06/2025 APPROVED Review Details

Outstanding Inspections

Permit Status: Inspections
Permit Number: TC-RES-0225-01111
Permite Description: Home owner had seen smoke in kitchen area and called fire department. Fire department Had used thermal imaging and found three hot spots in ceiling. After removing ceiling and located the old metal clad cable that was overheated and causing smoke, they called TEP to pull meter to de-energize panel. After meeting with insurance inspector was able to pin point the two electric runs that had to be replaced. All was safely removed and replace with new Romex 12/2 wire per NEC code.
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
03/07/2025 RSBU - Building Final N/A Re-inspection required 3/7/25: type NM cable shall not Embedded in cement, concrete, or aggregate.
03/07/2025 COT - RSEL - Electrical Final N/A Re-inspection required 3/7/25: type NM cable shall not Embedded in cement, concrete, or aggregate.

Completed Inspections

Permit Status: Inspections
Permit Number: TC-RES-0225-01111
Permit Description: Home owner had seen smoke in kitchen area and called fire department. Fire department Had used thermal imaging and found three hot spots in ceiling. After removing ceiling and located the old metal clad cable that was overheated and causing smoke, they called TEP to pull meter to de-energize panel. After meeting with insurance inspector was able to pin point the two electric runs that had to be replaced. All was safely removed and replace with new Romex 12/2 wire per NEC code.
Total Completed Inspections - 2
Date Description Inspector Results Comments
03/07/2025 COT - BULD - SWG Clearance Passed 3/7/25: SWG CLEARANCE
03/07/2025 BULD - Electrical Clearance Passed 3/7/25: TEP RECN CLEARANCE