Permit Details

Status:
Inspections
Type:
Model Building Permit
Address NEW:
9989 E LEBARON DR
Apply Date:
02/26/2026
Applicant:
Celina Rodriguez
Description:
Mirador Ridge Skies 2013 Plan (Model master plan TC-MDP-0825-00417)

Permit Reviews

Permit Number - TC-MDP-0925-00520
Permit Status: Inspections
Permit Description: Mirador Ridge Skies 2013 Plan (Model master plan TC-MDP-0825-00417)
Start Date Submittal Complete Date Status  
03/04/2026 SITE FROM MODEL PERMIT - SUBDIVISION v.1 03/16/2026 APPROVED Review Details
07/28/2026 SPECIAL INSPECTION REVIEW v.1 07/29/2026 APPROVED Review Details

Conditions

Permit Number - TC-MDP-0925-00520
Permit Status: Inspections
Permit Description: Mirador Ridge Skies 2013 Plan (Model master plan TC-MDP-0825-00417)
Date Description Comments
09/02/2025 Submit the Air Leakage & Duct Tightness Test Report completed by an Approved Special Inspector prior to Final Inspections.
03/06/2026 SPECIAL INSPECTION FOR CONCRETE INSTALLATION IS REQUIRED.
09/02/2025 Contractor with active Arizona Contractor's License for specified scope of work, or a signed Owner Builder Affidavit is required prior to issuance of permit. The Affidavit form is available at https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Residential-Permits. Contractor or Owner must have a TDC Online account and be added to the permit as the correct contact type https://www.tucsonaz.gov/files/sharedassets/public/v/2/pdsd/documents/tdc-faq/new-pdfs/adding-additional-contacts.pdf. If you are providing an Owner Builder Affidavit, the owner MUST be attached as a contact on the permit.
03/06/2026 SPECIAL INSPECTION FOR EPOXY ANCHORS IS REQUIRED.
09/02/2025 SPECIAL INSPECTION FOR POST TENSION SLAB IS REQUIRED.
03/06/2026 SPECIAL INSPECTION FOR REINFORCING STEEL AND/OR PRE-STRESSING TENDONS IS REQUIRED.
09/02/2025 Separate submittal to PC RWRD is required for new connections to sewer, new water meters and upsized water meters. For review and assessment: apply online at https://permits.pima.gov/ or contact us at sewer@pima.gov, (520) 724-9900.
09/02/2025 Sewer condition must be accepted and released by Pima County prior to issuance of a Temporary Certificate of Occupancy. For More Information visit https://www.pima.gov/1076/Sewer-Connection-Permits, To check your permit status https://permits.pima.gov/
03/06/2026 SPECIAL INSPECTION FOR SITE PREPARATION IS REQUIRED.

Outstanding Inspections

Permit Status: Inspections
Permit Number: TC-MDP-0925-00520
Permite Description: Mirador Ridge Skies 2013 Plan (Model master plan TC-MDP-0825-00417)
Total Outstanding Inspections - 7
Last Inspection Date Description Inspector Results Comments
07/15/2026 COT - RSEL - Outdoor Lighting N/A Re-inspection required 7-15-26 *doorbell appears to have no power * anti tip required at range, range is not installed. *Master bath left of sink counter top receptacle needs to be properly installed w/plate. * no running water at master bath sink. * Remove paint off of 20 minute rated tag at garage door. * Threshold at garage door must meet ADA requirements. * half hot receptacle in Northwest bedroom temper resistance compromised. * North bedroom at ceiling possible leak will need to repair. * properly terminate 90° fitting at PRV. * post tension tag required at hose bib. * lockout caps at refrigerant line located on floor AC unit must be properly installed. * address tag required at main panel. * attic, not walked due to needing a 10 foot ladder or better.
07/28/2026 ENGR Engineering Final N/A Not Ready Site is complete. Unsatisfied Conditions, needs submittals and approvals before passing.
07/15/2026 COT - RSPL - Plumbing Final N/A Re-inspection required 7-15-26 *doorbell appears to have no power * anti tip required at range, range is not installed. *Master bath left of sink counter top receptacle needs to be properly installed w/plate. * no running water at master bath sink. * Remove paint off of 20 minute rated tag at garage door. * Threshold at garage door must meet ADA requirements. * half hot receptacle in Northwest bedroom temper resistance compromised. * North bedroom at ceiling possible leak will need to repair. * properly terminate 90° fitting at PRV. * post tension tag required at hose bib. * lockout caps at refrigerant line located on floor AC unit must be properly installed. * address tag required at main panel. * attic, not walked due to needing a 10 foot ladder or better.
07/15/2026 RSBU - Building Progress N/A Re-inspection required 7-15-26 *doorbell appears to have no power * anti tip required at range, range is not installed. *Master bath left of sink counter top receptacle needs to be properly installed w/plate. * no running water at master bath sink. * Remove paint off of 20 minute rated tag at garage door. * Threshold at garage door must meet ADA requirements. * half hot receptacle in Northwest bedroom temper resistance compromised. * North bedroom at ceiling possible leak will need to repair. * properly terminate 90° fitting at PRV. * post tension tag required at hose bib. * lockout caps at refrigerant line located on floor AC unit must be properly installed. * address tag required at main panel. * attic, not walked due to needing a 10 foot ladder or better.
07/15/2026 COT - RSEL - Electrical Final N/A Re-inspection required 7-15-26 *doorbell appears to have no power * anti tip required at range, range is not installed. *Master bath left of sink counter top receptacle needs to be properly installed w/plate. * no running water at master bath sink. * Remove paint off of 20 minute rated tag at garage door. * Threshold at garage door must meet ADA requirements. * half hot receptacle in Northwest bedroom temper resistance compromised. * North bedroom at ceiling possible leak will need to repair. * properly terminate 90° fitting at PRV. * post tension tag required at hose bib. * lockout caps at refrigerant line located on floor AC unit must be properly installed. * address tag required at main panel. * attic, not walked due to needing a 10 foot ladder or better.
07/15/2026 COT - RSME - Mechanical Final N/A Re-inspection required 7-15-26 *doorbell appears to have no power * anti tip required at range, range is not installed. *Master bath left of sink counter top receptacle needs to be properly installed w/plate. * no running water at master bath sink. * Remove paint off of 20 minute rated tag at garage door. * Threshold at garage door must meet ADA requirements. * half hot receptacle in Northwest bedroom temper resistance compromised. * North bedroom at ceiling possible leak will need to repair. * properly terminate 90° fitting at PRV. * post tension tag required at hose bib. * lockout caps at refrigerant line located on floor AC unit must be properly installed. * address tag required at main panel. * attic, not walked due to needing a 10 foot ladder or better.
07/15/2026 RSBU - Building Final N/A Re-inspection required 7-15-26 *doorbell appears to have no power * anti tip required at range, range is not installed. *Master bath left of sink counter top receptacle needs to be properly installed w/plate. * no running water at master bath sink. * Remove paint off of 20 minute rated tag at garage door. * Threshold at garage door must meet ADA requirements. * half hot receptacle in Northwest bedroom temper resistance compromised. * North bedroom at ceiling possible leak will need to repair. * properly terminate 90° fitting at PRV. * post tension tag required at hose bib. * lockout caps at refrigerant line located on floor AC unit must be properly installed. * address tag required at main panel. * attic, not walked due to needing a 10 foot ladder or better.

Completed Inspections

Permit Status: Inspections
Permit Number: TC-MDP-0925-00520
Permit Description: Mirador Ridge Skies 2013 Plan (Model master plan TC-MDP-0825-00417)
Total Completed Inspections - 20
Date Description Inspector Results Comments
03/20/2026 COT - RSPL - Yard Water Line Passed 03/20/2026
Holding under test. Ok to backfill, shading required.
03/20/2026 COT - RSPL - Rough Soil Passed 03/20/2026
Holding under test. Ok to backfill, shading required.
04/06/2026 COT - RSEL - Electrical Underground Passed
04/07/2026 COT - RSBU - Excavation/Rebar/Zoning Passed 04/07/2026
Corrections made, ok to pour.
04/07/2026 COT - RSBU - Preslab Passed 04/07/2026
Corrections made, ok to pour.
04/16/2026 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed
04/16/2026 COT - RSBU - Roof Nailing Passed
05/07/2026 COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. Passed
05/07/2026 COT - RSEL - Grounding/Bonding Passed
05/07/2026 COT - RSPL - Gas Pressure Test Passed
05/07/2026 BULD - Electrical Clearance Passed 5.7.26
Approved
05/21/2026 COT - RSBU - Interior Shear Bracing Passed Passed 5/21/26
06/17/2026 COT - RSPL - Sewer Passed
06/26/2026 COT - BULD - SWG Clearance Passed approved for SWG clearance
07/28/2026 COT - RSEL - Outdoor Lighting Passed
07/28/2026 COT - RSPL - Plumbing Final Passed
07/28/2026 RSBU - Building Progress Passed
07/29/2026 COT - RSEL - Electrical Final Passed
07/30/2026 COT - RSME - Mechanical Final Passed Approved corrections were made. 7/30/2026
07/30/2026 RSBU - Building Final Passed Approved corrections were made. 7/30/2026

Documents

File Name Document Type  
FINAL SIC - MIRADOR RIDGE SKIES LOT 163-2026-07-21_V1.PDF DOCUMENTS VIEW
COFT - PDSD - PERMIT CARD (SSRS).PDF DOCUMENTS VIEW
MIRADOR RIDGE - LOT 163 START_V1.PDF DOCUMENTS VIEW
MRS 163 SIC-2026-02-26_V1.PDF DOCUMENTS VIEW