Permit: TC-MDP-0526-00362
Permit Details
Status:
Inspections
Type:
Model Building Permit
Address:
10021 E LEBARON DR
Address NEW:
10021 E LEBARON DR
Apply Date:
06/01/2026
Applicant:
Celina Rodriguez
Description:
Mirador Ridge Blossom 1728 Plan (Model master plan TC-MDP-0725-00411)
Permit Reviews
Permit Number - TC-MDP-0526-00362
Permit Status: Inspections
Permit Description: Mirador Ridge Blossom 1728 Plan (Model master plan TC-MDP-0725-00411)
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 06/03/2026 | SITE FROM MODEL PERMIT - SUBDIVISION v.1 | 06/10/2026 | APPROVED |
Outstanding Activity Conditions
Permit Number - TC-MDP-0526-00362
Permit Status: Inspections
Permit Description: Mirador Ridge Blossom 1728 Plan (Model master plan TC-MDP-0725-00411)
Total Outstanding Activity Conditions - 4
| Date | Name |
|---|---|
| 05/26/2026 | Submit the Air Leakage & Duct Tightness Test Report completed by an Approved Special Inspector prior to Final Inspections. |
| 05/26/2026 | SPECIAL INSPECTION FOR POST TENSION SLAB IS REQUIRED. |
| 06/09/2026 | Post-Installed Anchor Inspection Report is required. |
| 06/09/2026 | Post-Tension Inspection Report is required. |
Conditions
Permit Number - TC-MDP-0526-00362
Permit Status: Inspections
Permit Description: Mirador Ridge Blossom 1728 Plan (Model master plan TC-MDP-0725-00411)
| Date | Description | Comments |
|---|---|---|
| 05/26/2026 | Separate submittal to PC RWRD is required for new connections to sewer, new water meters and upsized water meters. For review and assessment: apply online at https://permits.pima.gov/ or contact us at sewer@pima.gov, (520) 724-9900. | |
| 05/26/2026 | Truss/Joist Design plans must be submitted and approved prior to intermediate inspections if residential building or finaling the permit if commercial building. |
Outstanding Inspections
Permit Status: Inspections
Permit Number: TC-MDP-0526-00362
Permite Description: Mirador Ridge Blossom 1728 Plan (Model master plan TC-MDP-0725-00411)
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/15/2026 | COT - RSBU - Roof Nailing | N/A | Re-inspection required | 7/15/26: nailing at shear wall over-spaced sw9 6/12 (fasteners shall be no closer than 3/8" from edge), properly secure king stud to trimmer per detail 13A, missing nails at rsp4 throughout at exterior, opening at entrance must have 2x6 header with DTC clip, anchor bolts must be placed no closer than 3.5" from edge of plate, shiners at shearwall, anchor bolts at sw11 must be 23" o.c with 3x3 washer plate, fasteners at shearwall shall not penemore than 1/8" and shall be further than 3/8" from edge, sw11 4/12" fasteners spacing throughout, rsp4 required at cripple studs and headers at window openings, 2 anchor bolts required at sill plate greater than 12", anchor shall be placed in middle third of sill plate, back patio requires (4)16 d nails at 24" o.c, sw9 at bedroom requires prop fasteners 6/12, garage satraps require (2) cs14 with opening greater than 9'. STOPPED INSPECTION MORE ITEMS MAY BE ADDED (Inside of home was not walked) |
| 07/15/2026 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | N/A | Re-inspection required | 7/15/26: nailing at shear wall over-spaced sw9 6/12 (fasteners shall be no closer than 3/8" from edge), properly secure king stud to trimmer per detail 13A, missing nails at rsp4 throughout at exterior, opening at entrance must have 2x6 header with DTC clip, anchor bolts must be placed no closer than 3.5" from edge of plate, shiners at shearwall, anchor bolts at sw11 must be 23" o.c with 3x3 washer plate, fasteners at shearwall shall not penemore than 1/8" and shall be further than 3/8" from edge, sw11 4/12" fasteners spacing throughout, rsp4 required at cripple studs and headers at window openings, 2 anchor bolts required at sill plate greater than 12", anchor shall be placed in middle third of sill plate, back patio requires (4)16 d nails at 24" o.c, sw9 at bedroom requires prop fasteners 6/12, garage satraps require (2) cs14 with opening greater than 9'. STOPPED INSPECTION MORE ITEMS MAY BE ADDED (Inside of home was not walked) |
Completed Inspections
Permit Status: Inspections
Permit Number: TC-MDP-0526-00362
Permit Description: Mirador Ridge Blossom 1728 Plan (Model master plan TC-MDP-0725-00411)
Total Completed Inspections - 7
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/24/2026 | COT - RSPL - Backwater Valve | Passed | ||
| 06/24/2026 | COT - RSPL - Rough Soil | Passed | ||
| 06/24/2026 | COT - RSPL - Sewer | Passed | ||
| 06/24/2026 | COT - RSPL - Yard Water Line | Passed | ||
| 07/02/2026 | COT - RSBU - Preslab | Passed | 07/02/2026 Approved per plan. Okay for concrete placement. |
|
| 07/02/2026 | COT - RSEL - Electrical Underground | Passed | ||
| 07/02/2026 | COT - RSBU - Excavation/Rebar/Zoning | Passed |