Permit: TC-MDP-0526-00362

Parcel: 141155630


Addresses:

10021 E LEBARON DR

Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Date Description Inspector Results Comments
07/15/2026 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 7/15/26: nailing at shear wall over-spaced sw9 6/12 (fasteners shall be no closer than 3/8" from edge), properly secure king stud to trimmer per detail 13A, missing nails at rsp4 throughout at exterior, opening at entrance must have 2x6 header with DTC clip, anchor bolts must be placed no closer than 3.5" from edge of plate, shiners at shearwall, anchor bolts at sw11 must be 23" o.c with 3x3 washer plate, fasteners at shearwall shall not penemore than 1/8" and shall be further than 3/8" from edge, sw11 4/12" fasteners spacing throughout, rsp4 required at cripple studs and headers at window openings, 2 anchor bolts required at sill plate greater than 12", anchor shall be placed in middle third of sill plate, back patio requires (4)16 d nails at 24" o.c, sw9 at bedroom requires prop fasteners 6/12, garage satraps require (2) cs14 with opening greater than 9'. STOPPED INSPECTION MORE ITEMS MAY BE ADDED
(Inside of home was not walked)