Description:
Great Sand Dunes SFR Model Escalara

Permit Reviews

Permit Number - TC-MDP-0524-00657
Permit Status: Inspections
Permit Description: Great Sand Dunes SFR Model Escalara
Start Date Submittal Complete Date Status  
05/30/2024 SITE FROM MODEL PERMIT - PRODUCTION v.1 06/03/2024 APPROVED Review Details

Outstanding Activity Conditions

Permit Number - TC-MDP-0524-00657
Permit Status: Inspections
Permit Description: Great Sand Dunes SFR Model Escalara
Total Outstanding Activity Conditions - 5
Date Name
05/28/2024 Sewer condition must be accepted and released by Pima County prior to issuance of a Temporary Certificate of Occupancy.
06/03/2024 SPECIAL INSPECTION FOR EPOXY ANCHORS IS REQUIRED.
06/03/2024 SPECIAL INSPECTION FOR POST TENSION SLAB IS REQUIRED.
06/03/2024 Post-Tension Inspection Report is required.
06/03/2024 SPECIAL INSPECTION FOR SPECIAL GRADING, EXCAVATION AND FILLING IS REQUIRED.

Conditions

Permit Number - TC-MDP-0524-00657
Permit Status: Inspections
Permit Description: Great Sand Dunes SFR Model Escalara
Date Description Comments
06/03/2024 Contractor with active Arizona Contractor's License for specified scope of work, or a signed Owner Builder Affidavit https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/residential-permits/pdsd_owner_builder_affidavit_081623.pdf, is required prior to issuance of permit. Contractor or Owner must have a TDC Online account and be added to the permit as the correct contact type https://www.tucsonaz.gov/files/sharedassets/public/v/2/pdsd/documents/tdc-faq/new-pdfs/adding-additional-contacts.pdf. If you are providing an Owner Builder Affidavit, the owner MUST be attached as a contact on the permit.
05/28/2024 Separate submittal to PC RWRD is required for new connections to sewer, new water meters and upsized water meters. Contact sewer@pima.gov for review and assessment.
06/03/2024 Truss/Joist Design plans must be submitted and approved prior to intermediate inspections if residential building or finaling the permit if commercial building.

Outstanding Inspections

Permit Status: Inspections
Permit Number: TC-MDP-0524-00657
Permite Description: Great Sand Dunes SFR Model Escalara
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
10/14/2024 COT - RSBU - Exterior Clips/Sheathing N/A Re-inspection required 10/14/24: wrong amount of trimmers at back sliding glass door frame. Anchor bolts at shear wall 9 not to plans. Rsp clip needs nailing at back south east corner. Floor trust at 2nd bearing point in garage need h25 clips. Shear wall 7 second floor bottom plate nailing not to schedule stopped inspection can add more at next inspection
10/14/2024 COT - RSBU - Roof Nailing N/A Re-inspection required 10/14/24: wrong amount of trimmers at back sliding glass door frame. Anchor bolts at shear wall 9 not to plans. Rsp clip needs nailing at back south east corner. Floor trust at 2nd bearing point in garage need h25 clips. Shear wall 7 second floor bottom plate nailing not to schedule stopped inspection can add more at next inspection

Completed Inspections

Permit Status: Inspections
Permit Number: TC-MDP-0524-00657
Permit Description: Great Sand Dunes SFR Model Escalara
Total Completed Inspections - 10
Date Description Inspector Results Comments
09/11/2024 COT - RSPL - Backwater Valve Passed Under plumbing is installed and connected to main sewer line. Backwater valve is installed between two clean outs. Entire system is under a water test with no leaks.
09/11/2024 COT - RSPL - Rough Soil Passed Under plumbing is installed and connected to main sewer line. Backwater valve is installed between two clean outs. Entire system is under a water test with no leaks.
09/11/2024 COT - RSPL - Sewer Passed Under plumbing is installed and connected to main sewer line. Backwater valve is installed between two clean outs. Entire system is under a water test with no leaks.
09/20/2024 COT - RSBU - Excavation/Rebar/Zoning Passed
09/20/2024 COT - RSBU - Preslab Passed
09/20/2024 COT - RSEL - Electrical Underground Passed
09/20/2024 COT - RSPL - Yard Water Line Passed
09/20/2024 COT - RSEL - Grounding/Bonding Passed
10/21/2024 COT - RSBU - Exterior Clips/Sheathing Passed 10/21/24: All items noted on last inspection have been corrected. Okay to proceed with rough-in of M, P, AND E.
10/21/2024 COT - RSBU - Roof Nailing Passed 10/21/24: All items noted on last inspection have been corrected. Okay to proceed with rough-in of M, P, AND E.