Permit: TC-MDP-0524-00651
Permit Details
Apply Date:
06/21/2024
Applicant:
Brianna Quiroz
Description:
Big Bend Model Plan La Escalera
Permit Reviews
Permit Number - TC-MDP-0524-00651
Permit Status: Inspections
Permit Description: Big Bend Model Plan La Escalera
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
06/21/2024 | SITE FROM MODEL PERMIT - PRODUCTION v.1 | 06/25/2024 | APPROVED |
Outstanding Activity Conditions
Permit Number - TC-MDP-0524-00651
Permit Status: Inspections
Permit Description: Big Bend Model Plan La Escalera
Total Outstanding Activity Conditions - 5
Date | Name |
---|---|
05/24/2024 | Sewer condition must be accepted and released by Pima County prior to issuance of a Temporary Certificate of Occupancy. |
06/24/2024 | SPECIAL INSPECTION FOR EPOXY ANCHORS IS REQUIRED. |
06/24/2024 | SPECIAL INSPECTION FOR POST TENSION SLAB IS REQUIRED. |
06/24/2024 | Post-Tension Inspection Report is required. |
06/24/2024 | SPECIAL INSPECTION FOR SPECIAL GRADING, EXCAVATION AND FILLING IS REQUIRED. |
Conditions
Permit Number - TC-MDP-0524-00651
Permit Status: Inspections
Permit Description: Big Bend Model Plan La Escalera
Date | Description | Comments |
---|---|---|
06/25/2024 | Contractor with active Arizona Contractor's License for specified scope of work, or a signed Owner Builder Affidavit https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/residential-permits/pdsd_owner_builder_affidavit_081623.pdf, is required prior to issuance of permit. Contractor or Owner must have a TDC Online account and be added to the permit as the correct contact type https://www.tucsonaz.gov/files/sharedassets/public/v/2/pdsd/documents/tdc-faq/new-pdfs/adding-additional-contacts.pdf. If you are providing an Owner Builder Affidavit, the owner MUST be attached as a contact on the permit. | |
05/24/2024 | Separate submittal to PC RWRD is required for new connections to sewer, new water meters and upsized water meters. Contact sewer@pima.gov for review and assessment. | |
06/24/2024 | Truss/Joist Design plans must be submitted and approved prior to intermediate inspections if residential building or finaling the permit if commercial building. |
Outstanding Inspections
Permit Status: Inspections
Permit Number: TC-MDP-0524-00651
Permite Description: Big Bend Model Plan La Escalera
Total Outstanding Inspections - 7
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/21/2024 | COT - RSPL - Yard Water Line | N/A | Partial Pass | PARTIAL PASS--Water meter is not installed and water line to house is under 60# psi pressure with no leaks. Okay to shade pipe and backfill trench. |
01/29/2025 | BULD - Electrical Clearance | N/A | Not Ready | 1/29/25 not ready, missing breakers for temp power |
01/29/2025 | COT - BULD - SWG Clearance | N/A | Not Applicable | n/a |
12/03/2024 | COT - RSBU - Exterior Clips/Sheathing | N/A | Re-inspection required | 12-3-24, missing shear walls at garage, nailing at shear wall near staircase and on north-side of dining room not per schedule- plans call for 2 inches on center. Also, A-35's throughout on second floor are not nailed flush to top plates and some are missing nails altogether |
12/03/2024 | COT - RSBU - Roof Nailing | N/A | Re-inspection required | 12-3-24, missing shear walls at garage,nailing at shear wall near staircase and on north-side of dining room not per schedule- plans call for 2 inches on center. Also, A-35's throughout on second floor are not nailed flush to top plates and some are missing nails altogether |
01/29/2025 | COT - RSPL - Gas Pressure Test | N/A | Not Applicable | n/a |
01/29/2025 | COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. | N/A | Not Ready | 1/29/25 DWV not under pressure, penetrations at vapor barrier not sealed throughout house and many are touching or very close to touch DWV pipes as well as thermostat lines. Possible leaks when put under test. Nail plate needed at thermostat at floor on second floor. Stopped intermediate. Electrical clearance also not ready. |
Completed Inspections
Permit Status: Inspections
Permit Number: TC-MDP-0524-00651
Permit Description: Big Bend Model Plan La Escalera
Total Completed Inspections - 8
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/21/2024 | COT - RSPL - Rough Soil | Passed | Underground plumbing is complete and under a water test with no leaks. Okay to shade pipe and backfill trenches. | |
10/21/2024 | COT - RSPL - Sewer | Passed | Sewer line is connected and under water pressure test with no leaks. Okay to shade pipe and backfill trench. | |
11/01/2024 | COT - RSBU - Excavation/Rebar/Zoning | Passed | 11-1-24, per approved plans. Okay to pour concrete. | |
11/01/2024 | COT - RSBU - Preslab | Passed | 11-1-24, pre slab per approved plans. Okay to pour concrete. | |
11/01/2024 | COT - RSEL - Electrical Underground | Passed | 11-1-24, per approved plans. Okay to pour concrete. | |
11/01/2024 | COT - RSEL - Grounding/Bonding | Passed | 11-1-24, per approved plans. Okay to pour concrete. | |
01/29/2025 | COT - RSBU - Exterior Clips/Sheathing | Passed | 1/29/25 pass | |
01/29/2025 | COT - RSBU - Roof Nailing | Passed | 1/29/25 pass |
Scheduled Inspections
Scheduled Inspections - TC-MDP-0524-00651
Status: Inspections
Description: Big Bend Model Plan La Escalera
Scheduled Date | Description | Entered By | Entered Date |
---|---|---|---|
01/31/2025 | COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. | Scheduled |