Permit Details

Status:
Inspections
Type:
Model Building Permit
Address NEW:
9875 E NALA PEAK WY
Apply Date:
04/10/2026
Applicant:
Celina Rodriguez
Description:
Mirador Ridge Skies 2201 (Model master plan TC-MDP-0825-00468)

Permit Reviews

Permit Number - TC-MDP-0226-00049
Permit Status: Inspections
Permit Description: Mirador Ridge Skies 2201 (Model master plan TC-MDP-0825-00468)
Start Date Submittal Complete Date Status  
04/15/2026 SITE FROM MODEL PERMIT - SUBDIVISION v.1 04/23/2026 REQUIRES RESUBMIT Review Details
04/24/2026 SITE FROM MODEL PERMIT - SUBDIVISION v.2 04/24/2026 APPROVED Review Details

Outstanding Activity Conditions

Permit Number - TC-MDP-0226-00049
Permit Status: Inspections
Permit Description: Mirador Ridge Skies 2201 (Model master plan TC-MDP-0825-00468)
Total Outstanding Activity Conditions - 5
Date Name
02/04/2026 Submit the Air Leakage & Duct Tightness Test Report completed by an Approved Special Inspector prior to Final Inspections.
02/04/2026 SPECIAL INSPECTION FOR POST TENSION SLAB IS REQUIRED.
02/04/2026 Sewer condition must be accepted and released by Pima County prior to issuance of a Temporary Certificate of Occupancy. For More Information visit https://www.pima.gov/1076/Sewer-Connection-Permits, To check your permit status https://permits.pima.gov/
04/24/2026 Post-Installed Anchor Inspection Report is required.
04/24/2026 SPECIAL INSPECTION FOR SITE PREPARATION IS REQUIRED.

Conditions

Permit Number - TC-MDP-0226-00049
Permit Status: Inspections
Permit Description: Mirador Ridge Skies 2201 (Model master plan TC-MDP-0825-00468)
Date Description Comments
02/04/2026 Separate submittal to PC RWRD is required for new connections to sewer, new water meters and upsized water meters. For review and assessment: apply online at https://permits.pima.gov/ or contact us at sewer@pima.gov, (520) 724-9900.
02/04/2026 Truss/Joist Design plans must be submitted and approved prior to intermediate inspections if residential building or finaling the permit if commercial building.

Outstanding Inspections

Permit Status: Inspections
Permit Number: TC-MDP-0226-00049
Permite Description: Mirador Ridge Skies 2201 (Model master plan TC-MDP-0825-00468)
Total Outstanding Inspections - 4
Last Inspection Date Description Inspector Results Comments
06/10/2026 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing N/A Re-inspection required Sw11's are not per plans
Shotpins missing at ends of plates throughout
07/01/2026 COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. N/A Re-inspection required 7/1/26: UFER ground must be properly terminated and accessible, address tag required at panel, properly secure temp receptacle, blank at open deathfront required, nail plates required throughout where plumbing/electrical come within 1 1/4" of stud face, DWV NOT UNDER TEST, PROPERLY PEX AT BATHROOM EAST, over notched studs in bathroom non-bearing wall, bathroom east wall needs fha structural plate, Boca plate required south wall of restroom, 3/4" pex required to have r3 insulation at hot water lines, pex supports required 32" horizontal and 48" vertical throughout, flex duct supports required 4' o.c, fix required at mechanical trusses that have notches for electrical , condensate drain must be properly sloped @ bedroom #4, properly secure secondary drain at bedroom 4, fix tear at duct master closet. Refrigerant lines at kitchen making contact at fha plate, refrigerant lines must be properly supported at attic, GAS PRESSURE TEXT MUST BE 15PSI, mark dryer vent box for feet installed, properly support dryer vent at entry (no tape).STOPPED INSPECTION ELECTRICAL WAS NOT WALKED. MORE ITEMS MAY BE ADDED.
07/01/2026 BULD - Electrical Clearance N/A Re-inspection required 7/1/26: UFER ground must be properly terminated and accessible, address tag required at panel, properly secure temp receptacle, blank at open deathfront required, nail plates required throughout where plumbing/electrical come within 1 1/4" of stud face, DWV NOT UNDER TEST, PROPERLY PEX AT BATHROOM EAST, over notched studs in bathroom non-bearing wall, bathroom east wall needs fha structural plate, Boca plate required south wall of restroom, 3/4" pex required to have r3 insulation at hot water lines, pex supports required 32" horizontal and 48" vertical throughout, flex duct supports required 4' o.c, fix required at mechanical trusses that have notches for electrical , condensate drain must be properly sloped @ bedroom #4, properly secure secondary drain at bedroom 4, fix tear at duct master closet. Refrigerant lines at kitchen making contact at fha plate, refrigerant lines must be properly supported at attic, GAS PRESSURE TEXT MUST BE 15PSI, mark dryer vent box for feet installed, properly support dryer vent at entry (no tape).STOPPED INSPECTION ELECTRICAL WAS NOT WALKED. MORE ITEMS MAY BE ADDED.
07/01/2026 COT - RSPL - Gas Pressure Test N/A Re-inspection required 7/1/26: UFER ground must be properly terminated and accessible, address tag required at panel, properly secure temp receptacle, blank at open deathfront required, nail plates required throughout where plumbing/electrical come within 1 1/4" of stud face, DWV NOT UNDER TEST, PROPERLY PEX AT BATHROOM EAST, over notched studs in bathroom non-bearing wall, bathroom east wall needs fha structural plate, Boca plate required south wall of restroom, 3/4" pex required to have r3 insulation at hot water lines, pex supports required 32" horizontal and 48" vertical throughout, flex duct supports required 4' o.c, fix required at mechanical trusses that have notches for electrical , condensate drain must be properly sloped @ bedroom #4, properly secure secondary drain at bedroom 4, fix tear at duct master closet. Refrigerant lines at kitchen making contact at fha plate, refrigerant lines must be properly supported at attic, GAS PRESSURE TEXT MUST BE 15PSI, mark dryer vent box for feet installed, properly support dryer vent at entry (no tape).STOPPED INSPECTION ELECTRICAL WAS NOT WALKED. MORE ITEMS MAY BE ADDED.

Completed Inspections

Permit Status: Inspections
Permit Number: TC-MDP-0226-00049
Permit Description: Mirador Ridge Skies 2201 (Model master plan TC-MDP-0825-00468)
Total Completed Inspections - 9
Date Description Inspector Results Comments
05/19/2026 COT - RSPL - Rough Soil Passed
05/19/2026 COT - RSPL - Backwater Valve Passed
05/20/2026 COT - RSPL - Yard Water Line Passed
05/27/2026 COT - RSBU - Excavation/Rebar/Zoning Passed
05/27/2026 COT - RSBU - Preslab Passed
05/27/2026 COT - RSEL - Electrical Underground Passed
06/10/2026 COT - RSBU - Roof Nailing Passed
06/11/2026 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed
06/22/2026 COT - RSPL - Sewer Passed

Documents

File Name Document Type  
COFT - PDSD - PERMIT CARD (SSRS).PDF DOCUMENTS VIEW
MIRADOR RIDGE - LOT 177 START_V1.PDF DOCUMENTS VIEW
MRS 177 SIC-2026-04-23_V2.PDF DOCUMENTS VIEW
RECEIPT_WAIT1SEC_V1.PDF DOCUMENTS VIEW