Permit: TC-MDP-0226-00049
Permit Details
Status:
Inspections
Type:
Model Building Permit
Address:
9875 E NALA PEAK WY
Address NEW:
9875 E NALA PEAK WY
Apply Date:
04/10/2026
Applicant:
Celina Rodriguez
Description:
Mirador Ridge Skies 2201 (Model master plan TC-MDP-0825-00468)
Permit Reviews
Permit Number - TC-MDP-0226-00049
Permit Status: Inspections
Permit Description: Mirador Ridge Skies 2201 (Model master plan TC-MDP-0825-00468)
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 04/15/2026 | SITE FROM MODEL PERMIT - SUBDIVISION v.1 | 04/23/2026 | REQUIRES RESUBMIT |
| 04/24/2026 | SITE FROM MODEL PERMIT - SUBDIVISION v.2 | 04/24/2026 | APPROVED |
Outstanding Activity Conditions
Permit Number - TC-MDP-0226-00049
Permit Status: Inspections
Permit Description: Mirador Ridge Skies 2201 (Model master plan TC-MDP-0825-00468)
Total Outstanding Activity Conditions - 5
| Date | Name |
|---|---|
| 02/04/2026 | Submit the Air Leakage & Duct Tightness Test Report completed by an Approved Special Inspector prior to Final Inspections. |
| 02/04/2026 | SPECIAL INSPECTION FOR POST TENSION SLAB IS REQUIRED. |
| 02/04/2026 | Sewer condition must be accepted and released by Pima County prior to issuance of a Temporary Certificate of Occupancy. For More Information visit https://www.pima.gov/1076/Sewer-Connection-Permits, To check your permit status https://permits.pima.gov/ |
| 04/24/2026 | Post-Installed Anchor Inspection Report is required. |
| 04/24/2026 | SPECIAL INSPECTION FOR SITE PREPARATION IS REQUIRED. |
Conditions
Permit Number - TC-MDP-0226-00049
Permit Status: Inspections
Permit Description: Mirador Ridge Skies 2201 (Model master plan TC-MDP-0825-00468)
| Date | Description | Comments |
|---|---|---|
| 02/04/2026 | Separate submittal to PC RWRD is required for new connections to sewer, new water meters and upsized water meters. For review and assessment: apply online at https://permits.pima.gov/ or contact us at sewer@pima.gov, (520) 724-9900. | |
| 02/04/2026 | Truss/Joist Design plans must be submitted and approved prior to intermediate inspections if residential building or finaling the permit if commercial building. |
Outstanding Inspections
Permit Status: Inspections
Permit Number: TC-MDP-0226-00049
Permite Description: Mirador Ridge Skies 2201 (Model master plan TC-MDP-0825-00468)
Total Outstanding Inspections - 4
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/10/2026 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | N/A | Re-inspection required | Sw11's are not per plans Shotpins missing at ends of plates throughout |
| 07/01/2026 | COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. | N/A | Re-inspection required | 7/1/26: UFER ground must be properly terminated and accessible, address tag required at panel, properly secure temp receptacle, blank at open deathfront required, nail plates required throughout where plumbing/electrical come within 1 1/4" of stud face, DWV NOT UNDER TEST, PROPERLY PEX AT BATHROOM EAST, over notched studs in bathroom non-bearing wall, bathroom east wall needs fha structural plate, Boca plate required south wall of restroom, 3/4" pex required to have r3 insulation at hot water lines, pex supports required 32" horizontal and 48" vertical throughout, flex duct supports required 4' o.c, fix required at mechanical trusses that have notches for electrical , condensate drain must be properly sloped @ bedroom #4, properly secure secondary drain at bedroom 4, fix tear at duct master closet. Refrigerant lines at kitchen making contact at fha plate, refrigerant lines must be properly supported at attic, GAS PRESSURE TEXT MUST BE 15PSI, mark dryer vent box for feet installed, properly support dryer vent at entry (no tape).STOPPED INSPECTION ELECTRICAL WAS NOT WALKED. MORE ITEMS MAY BE ADDED. |
| 07/01/2026 | BULD - Electrical Clearance | N/A | Re-inspection required | 7/1/26: UFER ground must be properly terminated and accessible, address tag required at panel, properly secure temp receptacle, blank at open deathfront required, nail plates required throughout where plumbing/electrical come within 1 1/4" of stud face, DWV NOT UNDER TEST, PROPERLY PEX AT BATHROOM EAST, over notched studs in bathroom non-bearing wall, bathroom east wall needs fha structural plate, Boca plate required south wall of restroom, 3/4" pex required to have r3 insulation at hot water lines, pex supports required 32" horizontal and 48" vertical throughout, flex duct supports required 4' o.c, fix required at mechanical trusses that have notches for electrical , condensate drain must be properly sloped @ bedroom #4, properly secure secondary drain at bedroom 4, fix tear at duct master closet. Refrigerant lines at kitchen making contact at fha plate, refrigerant lines must be properly supported at attic, GAS PRESSURE TEXT MUST BE 15PSI, mark dryer vent box for feet installed, properly support dryer vent at entry (no tape).STOPPED INSPECTION ELECTRICAL WAS NOT WALKED. MORE ITEMS MAY BE ADDED. |
| 07/01/2026 | COT - RSPL - Gas Pressure Test | N/A | Re-inspection required | 7/1/26: UFER ground must be properly terminated and accessible, address tag required at panel, properly secure temp receptacle, blank at open deathfront required, nail plates required throughout where plumbing/electrical come within 1 1/4" of stud face, DWV NOT UNDER TEST, PROPERLY PEX AT BATHROOM EAST, over notched studs in bathroom non-bearing wall, bathroom east wall needs fha structural plate, Boca plate required south wall of restroom, 3/4" pex required to have r3 insulation at hot water lines, pex supports required 32" horizontal and 48" vertical throughout, flex duct supports required 4' o.c, fix required at mechanical trusses that have notches for electrical , condensate drain must be properly sloped @ bedroom #4, properly secure secondary drain at bedroom 4, fix tear at duct master closet. Refrigerant lines at kitchen making contact at fha plate, refrigerant lines must be properly supported at attic, GAS PRESSURE TEXT MUST BE 15PSI, mark dryer vent box for feet installed, properly support dryer vent at entry (no tape).STOPPED INSPECTION ELECTRICAL WAS NOT WALKED. MORE ITEMS MAY BE ADDED. |
Completed Inspections
Permit Status: Inspections
Permit Number: TC-MDP-0226-00049
Permit Description: Mirador Ridge Skies 2201 (Model master plan TC-MDP-0825-00468)
Total Completed Inspections - 9
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/19/2026 | COT - RSPL - Rough Soil | Passed | ||
| 05/19/2026 | COT - RSPL - Backwater Valve | Passed | ||
| 05/20/2026 | COT - RSPL - Yard Water Line | Passed | ||
| 05/27/2026 | COT - RSBU - Excavation/Rebar/Zoning | Passed | ||
| 05/27/2026 | COT - RSBU - Preslab | Passed | ||
| 05/27/2026 | COT - RSEL - Electrical Underground | Passed | ||
| 06/10/2026 | COT - RSBU - Roof Nailing | Passed | ||
| 06/11/2026 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Passed | ||
| 06/22/2026 | COT - RSPL - Sewer | Passed |