Permit: TC-MDP-0223-00574
Permit Details
Apply Date:
06/13/2023
Applicant:
Daria Hopkins
Description:
SFR 135.2110 T21-M0053
Permit Reviews
Permit Number - TC-MDP-0223-00574
Permit Status: Complete
Permit Description: SFR 135.2110 T21-M0053
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
06/13/2023 | RESIDENTIAL NEW DWELLING v.1 | 06/15/2023 | APPROVED |
09/27/2023 | BUILDING DEFERRED SUBMITTAL REVIEW v.1 | 09/27/2023 | APPROVED |
03/26/2024 | BUILDING DEFERRED SUBMITTAL REVIEW v.1 | 03/26/2024 | APPROVED |
Conditions
Permit Number - TC-MDP-0223-00574
Permit Status: Complete
Permit Description: SFR 135.2110 T21-M0053
Date | Description | Comments |
---|---|---|
06/13/2023 | SPECIAL INSPECTION FOR EPOXY ANCHORS IS REQUIRED. | |
06/13/2023 | SPECIAL INSPECTION FOR POST TENSION SLAB IS REQUIRED. | |
09/27/2023 | Post-Tension Inspection Report is required. | |
06/13/2023 | Separate submittal to PC RWRD is required for new connections to sewer, new water meters and upsized water meters. Contact sewer@pima.gov for review and assessment. | |
06/13/2023 | SPECIAL INSPECTION FOR SPECIAL GRADING, EXCAVATION AND FILLING IS REQUIRED. | |
06/15/2023 | Truss/Joist Design plans must be submitted and approved prior to intermediate inspections if residential building or finaling the permit if commercial building. |
Outstanding Inspections
Permit Status: Complete
Permit Number: TC-MDP-0223-00574
Permite Description: SFR 135.2110 T21-M0053
Total Outstanding Inspections - 7
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/03/2024 | RSBU - Building Progress | N/A | Re-inspection required | 6/3/24: All exterior plastic piping must be coated for UV protection, clean out at drive way must be cut and capped, arch fault at washer missing, properly install exterior light fixtures at entrance, weather strip at front door missing, tape at b-vent at water heater, T&P discharge shall be on exterior 6" above grade, knockout plastic connectors required at disconnect box in attic and at air handler, air handler is being over amped (15Amp max). |
06/03/2024 | RSBU - Building Final | N/A | Re-inspection required | 6/3/24: All exterior plastic piping must be coated for UV protection, clean out at drive way must be cut and capped, arch fault at washer missing, properly install exterior light fixtures at entrance, weather strip at front door missing, tape at b-vent at water heater, T&P discharge shall be on exterior 6" above grade, knockout plastic connectors required at disconnect box in attic and at air handler, air handler is being over amped (15Amp max). |
06/03/2024 | COT - RSEL - Electrical Final | N/A | Re-inspection required | 6/3/24: All exterior plastic piping must be coated for UV protection, clean out at drive way must be cut and capped, arch fault at washer missing, properly install exterior light fixtures at entrance, weather strip at front door missing, tape at b-vent at water heater, T&P discharge shall be on exterior 6" above grade, knockout plastic connectors required at disconnect box in attic and at air handler, air handler is being over amped (15Amp max). |
06/03/2024 | COT - RSME - Mechanical Final | N/A | Re-inspection required | 6/3/24: All exterior plastic piping must be coated for UV protection, clean out at drive way must be cut and capped, arch fault at washer missing, properly install exterior light fixtures at entrance, weather strip at front door missing, tape at b-vent at water heater, T&P discharge shall be on exterior 6" above grade, knockout plastic connectors required at disconnect box in attic and at air handler, air handler is being over amped (15Amp max). |
06/03/2024 | COT - RSPL - Gas Final | N/A | Re-inspection required | 6/3/24: All exterior plastic piping must be coated for UV protection, clean out at drive way must be cut and capped, arch fault at washer missing, properly install exterior light fixtures at entrance, weather strip at front door missing, tape at b-vent at water heater, T&P discharge shall be on exterior 6" above grade, knockout plastic connectors required at disconnect box in attic and at air handler, air handler is being over amped (15Amp max). |
06/03/2024 | COT - RSPL - Plumbing Final | N/A | Re-inspection required | 6/3/24: All exterior plastic piping must be coated for UV protection, clean out at drive way must be cut and capped, arch fault at washer missing, properly install exterior light fixtures at entrance, weather strip at front door missing, tape at b-vent at water heater, T&P discharge shall be on exterior 6" above grade, knockout plastic connectors required at disconnect box in attic and at air handler, air handler is being over amped (15Amp max). |
06/03/2024 | COT - RSEL - Outdoor Lighting | N/A | Re-inspection required | 6/3/24: All exterior plastic piping must be coated for UV protection, clean out at drive way must be cut and capped, arch fault at washer missing, properly install exterior light fixtures at entrance, weather strip at front door missing, tape at b-vent at water heater, T&P discharge shall be on exterior 6" above grade, knockout plastic connectors required at disconnect box in attic and at air handler, air handler is being over amped (15Amp max). |
Completed Inspections
Permit Status: Complete
Permit Number: TC-MDP-0223-00574
Permit Description: SFR 135.2110 T21-M0053
Total Completed Inspections - 22