Parcel: 141433390

Inspection Status: Re-inspection required

Inspection History: RSBU - Building Final 

Permit Number - TC-MDP-0223-00574

Inspection Description - RSBU - Building Final 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
06/03/2024 RSBU - Building Final  Re-inspection required 6/3/24: All exterior plastic piping must be coated for UV protection, clean out at drive way must be cut and capped, arch fault at washer missing, properly install exterior light fixtures at entrance, weather strip at front door missing, tape at b-vent at water heater, T&P discharge shall be on exterior 6" above grade, knockout plastic connectors required at disconnect box in attic and at air handler, air handler is being over amped (15Amp max).
06/06/2024 RSBU - Building Final  Passed