Permit: TC-MDP-0223-00444
Permit Details
Apply Date:
02/03/2023
Applicant:
Daria Hopkins
Description:
SFR 230.2690 T21-M0027
Permit Reviews
Permit Number - TC-MDP-0223-00444
Permit Status: Complete
Permit Description: SFR 230.2690 T21-M0027
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
05/11/2023 | RESIDENTIAL NEW DWELLING v.1 | 05/15/2023 | APPROVED |
02/08/2024 | BUILDING DEFERRED SUBMITTAL REVIEW v.1 | 02/08/2024 | APPROVED |
Conditions
Permit Number - TC-MDP-0223-00444
Permit Status: Complete
Permit Description: SFR 230.2690 T21-M0027
Date | Description | Comments |
---|---|---|
05/15/2023 | Special inspections must be performed by an approved third party inspection agency at the owner's expense. Special inspection forms and reports are required to be submitted for review and approved prior to issuance of final approval documents. | |
05/11/2023 | SPECIAL INSPECTION FOR EPOXY ANCHORS IS REQUIRED. | |
05/11/2023 | SPECIAL INSPECTION FOR POST TENSION SLAB IS REQUIRED. | |
02/08/2024 | Post-Tension Inspection Report is required. | |
05/11/2023 | Separate submittal to PC RWRD is required for new connections to sewer, new water meters and upsized water meters. Contact sewer@pima.gov for review and assessment. | |
05/11/2023 | SPECIAL INSPECTION FOR SPECIAL GRADING, EXCAVATION AND FILLING IS REQUIRED. | |
05/15/2023 | Truss/Joist Design plans must be submitted and approved prior to intermediate inspections if residential building or finaling the permit if commercial building. |
Outstanding Inspections
Permit Status: Complete
Permit Number: TC-MDP-0223-00444
Permite Description: SFR 230.2690 T21-M0027
Total Outstanding Inspections - 3
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/13/2023 | COT - RSBU - Exterior Clips/Sheathing | N/A | Re-inspection required | 9/11/23: missing anchor bolts at shear wall, HTT4 not installed at shear walls, missing RSP clips, MASA clips missing nailing STOPPED INSPECTION 9/13/23 not ready still missing the above notes |
10/27/2023 | COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. | N/A | Re-inspection required | Missing clean out in kitchen pantry, nail plate needed right side of garage, open chase left side of garage, can lights must be 12” away from water lines or insulate water lines, top plate in kitchen pantry over notched and needs bang plate and foam, add nail plate at top plate for 220v wire for range, bed. 2 staple wire needed and fix wiring, bang plate needed for vent in bath. 3, support 4-gang box in loft, connect and secure furnace line in loft ceiling, nail plates needed in loft, nail plates needed in master bedroom, support 4-gang box in master bathroom. |
01/16/2024 | COT - BULD - SWG Clearance | N/A | Re-inspection required | 1/16/24: missing shut off valve at kitchen |
Completed Inspections
Permit Status: Complete
Permit Number: TC-MDP-0223-00444
Permit Description: SFR 230.2690 T21-M0027
Total Completed Inspections - 22