Permit Details

Status:
Complete
Type:
Commercial Building
Address:
1 E TOOLE AV
Apply Date:
11/21/2023
Applicant:
Chris Leighton
Description:
Application for C of O

Permit Reviews

Permit Number - TC-COM-1123-02704
Permit Status: Complete
Permit Description: Application for C of O
Start Date Submittal Complete Date Status  
09/12/2024 BUILDING DEFERRED SUBMITTAL REVIEW v.3 09/12/2024 APPROVED Review Details
03/21/2024 COMMERCIAL REVIEW - FULL v.1 04/22/2024 REQUIRES RESUBMIT Review Details
04/22/2024 COMMERCIAL REVIEW - FULL v.2 04/24/2024 APPROVED Review Details
07/24/2024 BUILDING DEFERRED SUBMITTAL REVIEW v.2 08/01/2024 REQUIRES RESUBMIT Review Details
03/16/2024 COMMERCIAL REVIEW - FULL v.4 03/21/2024 REQUIRES RESUBMIT Review Details
01/23/2024 COMMERCIAL REVIEW - FULL v.3 02/27/2024 REQUIRES RESUBMIT Review Details
12/14/2023 COMMERCIAL REVIEW - FULL v.2 01/09/2024 REQUIRES RESUBMIT Review Details
11/22/2023 COMMERCIAL REVIEW - FULL v.1 12/11/2023 REQUIRES RESUBMIT Review Details
07/18/2024 BUILDING DEFERRED SUBMITTAL REVIEW v.1 07/19/2024 REQUIRES RESUBMIT Review Details
04/24/2024 RESTAMP - COMMERCIAL v.1 04/25/2024 APPROVED Review Details

Conditions

Permit Number - TC-COM-1123-02704
Permit Status: Complete
Permit Description: Application for C of O
Date Description Comments
02/08/2024 Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit. Contractor must have a TDC Online account and be added to the permit as a contact.
04/22/2024 SPECIAL INSPECTION FOR FIELD WELDING IS REQUIRED.
02/08/2024 Restroom Appeal to the Building Official to be approved or additional facilities to be added prior to issuance.
02/08/2024 ADA ramp must be submitted, approved and ramp installed on site, with means of egress complete, prior to final inspections, T C of O and C of O
02/08/2024 SPECIAL INSPECTION OF FABRICATION OF STEEL STAIRWAY BEING PERFORMED ON THE PREMISES OF A FABRICATOR'S SHOP IS REQUIRED. EXCEPTION: SPECIAL INSPECTIONS OF FABRICATORS WITH ONE OF THE FOLLOWING QUALIFICATIONS IS NOT REQUIRED: • INTERNATIONAL ACCREDITATION SERVICE, INC. (IAS)APPROVED FABRICATOR. • AISC CERTIFIED FABRICATOR (STD). THE SPECIAL INSPECTOR SHALL VERIFY THAT THE FABRICATOR MAINTAINS DETAILED FABRICATION AND QUALITY CONTROL PROCEDURES THAT PROVIDE A BASIS FOR INSPECTION CONTROL OF THE WORKMANSHIP AND THE FABRICATOR’S ABILITY TO CONFORM TO APPROVED CONSTRUCTION DOCUMENTS AND REFERENCED STANDARDS. THE SPECIAL INSPECTOR SHALL REVIEW THE PROCEDURES FOR COMPLETENESS AND ADEQUACY RELATIVE TO THE CODE REQUIREMENTS FOR THE FABRICATOR’S SCOPE OF WORK.
02/12/2024 Steel Stairway Designs and calculations must be submitted, approved and stairway to be installed on site, with means of egress complete, prior to final inspections, T C of O and C of O

Outstanding Inspections

Permit Status: Complete
Permit Number: TC-COM-1123-02704
Permite Description: Application for C of O
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
07/15/2024 TRSP - ROW - Final/Close-Out N/A Re-inspection required
07/18/2024 ENGR Engineering Final N/A Not Ready The site has the following items wrong at this time:
1) The landing at the bottom of the ramp is noncompliant with the ADA code due to slopes exceeding the Maximum of over 2% in all directions, in areas it is 3% or greater because the adjoining concrete is noncompliant for cross slope. Also the required handrail for ramp has been extended on the righthand side approximately 4 to 5 feet farther. This will require the landing/directional change area will need to be after the handrail. This area is noncompliant because the slopes exceed 5% or more in the areas of existing concrete sidewalk within the City of Tucsons Right of Way.
2) At the current landing location there are 2 issues were the possibility of water being deposited directly onto the sidewalk from the existing roof drainage system. There are 2 drainage pipes at this location that will need to be modified to redirect the outflow to another area to be compliant. The first is an at grade 6” pipe just north at this location in the existing wall supporting the upper sidewalk. This pipe will need to be directed in the basement so that it can be brought out at a different location in this same wall that will not affect the pedestrian traffic. The second is an overhead drain pipe that has the outflow dropping on the current landing area which is a health and safety issue, as well as being a code violation which states the following No water within a 10 year storm can be deposited directly onto a pedestrian pathway, it is to be directed underneath the pedestrian pathways.”

The sidewalk within the Right of Way is non compliant in areas and may need to be modified to help eliminate some of the issues that this area is facing for non-compliance concerns, this will be discussed with the Transportation Department who over sees the Rights of Way for the City of Tucson.

Completed Inspections

Permit Status: Complete
Permit Number: TC-COM-1123-02704
Permit Description: Application for C of O
Total Completed Inspections - 10
Date Description Inspector Results Comments
06/07/2024 COT - FCON - Alarm - Final Passed Approved on 5/23/24 on permit TF-FCP-0324-00209
06/07/2024 COT - FCON - Sprinkler - Final Passed Approved on 12/21/23 on permit TF-FCP-1123-01322
07/10/2024 COT - FCON - Fire - Final Passed
07/11/2024 COT - LCBU - Building Final Passed
07/11/2024 COT - LCEL - Electrical Final Passed
07/11/2024 COT - LCME - Mechanical Final Passed
07/11/2024 COT - LCPL - Plumbing Final Passed
07/11/2024 COT - HCBU - CofO Passed OK to make application for Certificate of Occupancy.
07/11/2024 COT - HCBU - TCO Passed Ok to make application for Certificate of Occupancy.
07/11/2024 COT - LCBU - Framing Passed

Documents

File Name Document Type  
COFO_FINALCOFO_COMMERCIAL.PDF DOCUMENTS VIEW
COMMENT LETTER 1 E TOOLE VENUE 4-15-24_V1.PDF DOCUMENTS VIEW
WELDING SPECIAL INSPECTION REPORT-2024-07-17_V1.PDF DOCUMENTS VIEW
COFO_TEMPORARYCOFO.PDF DOCUMENTS VIEW
COFT - PDSD - PERMIT CARD.PDF DOCUMENTS VIEW
CONS-A-1 THRU L1 STONEBRIDGE EVENT CENTER 4-16-24 1 E TOOLE_V4.PDF DOCUMENTS VIEW