Permit Details

Status:
Issued
Type:
Commercial Building
Address NEW:
5639 E 5TH ST UNIT A
Apply Date:
11/13/2022
Applicant:
Cindy Calbimonte
Description:
Existing complex of four (4) office buildings with B type occupancy to be renovated to 16 single bedroom mulitfamily complex (4 units per building). No building foot print increase. Changes to exterior walls where new egress / openings required.

Permit Reviews

Permit Number - TC-COM-1122-00108
Permit Status: Issued
Permit Description: Existing complex of four (4) office buildings with B type occupancy to be renovated to 16 single bedroom mulitfamily complex (4 units per building). No building foot print increase. Changes to exterior walls where new egress / openings required.
Start Date Submittal Complete Date Status  
05/05/2025 COMMERCIAL REVIEW - FULL REVISION v.5 05/14/2025 APPROVED Review Details
03/13/2025 COMMERCIAL REVIEW - FULL REVISION v.3 03/13/2025 REQUIRES RESUBMIT Review Details
03/26/2025 COMMERCIAL REVIEW - FULL REVISION v.4 04/07/2025 REQUIRES RESUBMIT Review Details
12/17/2024 COMMERCIAL REVIEW - FULL v.1 12/19/2024 REQUIRES RESUBMIT Review Details
01/13/2025 COMMERCIAL REVIEW - FULL REVISION v.2 02/03/2025 REQUIRES RESUBMIT Review Details
05/14/2025 RESTAMP - COMMERCIAL v.1 05/19/2025 APPROVED Review Details
05/24/2023 COMMERCIAL REVIEW - FULL v.3 05/25/2023 APPROVED Review Details
08/04/2025 COMMERCIAL REVIEW - FULL REVISION v.2 08/25/2025 APPROVED Review Details
05/25/2023 RESTAMP - COMMERCIAL v.1 05/25/2023 APPROVED Review Details
06/16/2025 COMMERCIAL REVIEW - FULL REVISION v.1 06/20/2025 APPROVED Review Details
12/09/2022 COMMERCIAL REVIEW - FULL v.1 01/19/2023 REQUIRES RESUBMIT Review Details
08/04/2025 COMMERCIAL REVIEW - FULL REVISION v.1 08/04/2025 REQUIRES RESUBMIT Review Details
04/05/2023 COMMERCIAL REVIEW - FULL v.2 05/03/2023 REQUIRES RESUBMIT Review Details
01/13/2025 COMMERCIAL REVIEW - FULL REVISION v.1 01/13/2025 REQUIRES RESUBMIT Review Details

Outstanding Activity Conditions

Permit Number - TC-COM-1122-00108
Permit Status: Issued
Permit Description: Existing complex of four (4) office buildings with B type occupancy to be renovated to 16 single bedroom mulitfamily complex (4 units per building). No building foot print increase. Changes to exterior walls where new egress / openings required.
Total Outstanding Activity Conditions - 2
Date Name
09/27/2024 SPECIAL INSPECTION FOR CONCRETE INSTALLATION IS REQUIRED.
09/27/2024 Masonry Inspection Report submittal review is required.

Conditions

Permit Number - TC-COM-1122-00108
Permit Status: Issued
Permit Description: Existing complex of four (4) office buildings with B type occupancy to be renovated to 16 single bedroom mulitfamily complex (4 units per building). No building foot print increase. Changes to exterior walls where new egress / openings required.
Date Description Comments
04/21/2023 Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit.

Outstanding Inspections

Permit Status: Issued
Permit Number: TC-COM-1122-00108
Permite Description: Existing complex of four (4) office buildings with B type occupancy to be renovated to 16 single bedroom mulitfamily complex (4 units per building). No building foot print increase. Changes to exterior walls where new egress / openings required.
Total Outstanding Inspections - 11
Last Inspection Date Description Inspector Results Comments
11/19/2024 COT - HCBU - Building Above Ceiling N/A Not Applicable
09/03/2025 COT - BULD - SWG Clearance N/A Not Applicable
07/21/2025 COT - HCPL - Plumbing Progress N/A Partial Pass UG water
6-27-25: Unit's in building C-#1-4plumbing vents at bathroom vents not per plans-submit a revision or install vents per plans, secure/strap all DWV. Also, DWV must be under test and all penetrations at top plates must be firefoamed at time of inspection
7/21/25: plumbing underground per approved plans, DVW understands in walls. Ok to proceed.
12/03/2024 COT - HCBU - Building Progress N/A Re-inspection required 12-3-24: Work is continuing that is not shown on approved plans.
06/02/2026 COT - HCBU - Building Final N/A Re-inspection required 6/2/26: Water hammer arrestor required at dishwasher at all units, padlock required at water heater breakers, properly secure all raceways on exterior of building, 90 degree fitting on 3/4" conduit for outdoor lighting and receptacles must be replaced with approved wet location fittings, hot water lines in bathroom water heater required to have insulation on 3/4" pipe, fire finals required to be completed and passed prior to building final approval, engineering final approval required prior to building final approval, if TCO is required for Model units please provide a site plan for separation between construction and residence area, per number of units required we shall have the appropriate number of parking spaces for TCO. Revision required for cover hall between units.
06/02/2026 COT - HCBU - CofO N/A Re-inspection required 6/2/26: Water hammer arrestor required at dishwasher at all units, padlock required at water heater breakers, properly secure all raceways on exterior of building, 90 degree fitting on 3/4" conduit for outdoor lighting and receptacles must be replaced with approved wet location fittings, hot water lines in bathroom water heater required to have insulation on 3/4" pipe, fire finals required to be completed and passed prior to building final approval, engineering final approval required prior to building final approval, if TCO is required for Model units please provide a site plan for separation between construction and residence area, per number of units required we shall have the appropriate number of parking spaces for TCO. Revision required for cover hall between units.
COT - FCON - Alarm - Final N/A Not Ready
COT - FCON - Sprinkler - Final N/A Not Ready
COT - FCON - Fire - Final N/A Not Ready
06/09/2026 COT - HCEL - Electrical Final N/A Canceled
06/09/2026 COT - HCPL - Plumbing Final N/A Canceled

Completed Inspections

Permit Status: Issued
Permit Number: TC-COM-1122-00108
Permit Description: Existing complex of four (4) office buildings with B type occupancy to be renovated to 16 single bedroom mulitfamily complex (4 units per building). No building foot print increase. Changes to exterior walls where new egress / openings required.
Total Completed Inspections - 19
Date Description Inspector Results Comments
10/01/2024 COT - HCPL - Rough Soil Passed
07/14/2025 COT - HCBU - Roof Nailing Passed
09/03/2025 COT - HCBU - Framing Passed
09/09/2025 COT - HCEL - Electrical Intermediate Passed
09/09/2025 COT - HCEL - Electrical Above Ceiling Passed
09/09/2025 COT - HCME - Mechanical Intermediate Passed
09/09/2025 COT - HCPL - Plumbing Intermediate Passed
09/09/2025 COT - HCME - Mechanical Above Ceiling Passed
09/09/2025 COT - HCPL - Plumbing Above Ceiling Passed
09/24/2025 COT - HCEL - Electrical Underground Passed Approved underground electrical conduits from multi-meter pack to unit A (including conduit to future pads) okay to backfill progress areas
10/10/2025 COT - HCBU - Firewall/Fire Barrier/Firestop Passed
10/15/2025 BULD - Electrical Clearance Passed 10/15/25: ECO TEP CLEARANCE FOR 5639 E 5TH ST BLDG A (Units 1,2,3,4)
10/30/2025 COT - HCME - Mechanical Progress Passed
10/30/2025 COT - HCEL - Electrical Progress Passed
03/24/2026 COT - HCPL - Plumbing Progress Passed
03/24/2026 COT - HCBU - Building Progress Passed
05/22/2026 COT - HCME - Mechanical Final Passed
07/02/2026 COT - HCEL - Electrical Final Passed
07/02/2026 COT - HCPL - Plumbing Final Passed

Documents

File Name Document Type  
COFT - PDSD - PERMIT CARD.PDF DOCUMENTS VIEW
4_COT_REVISIONS NARRATIVE TC-COM-1222-00270_V1.PDF DOCUMENTS VIEW
4_RAH QUAD CD REV 2_V1.PDF DOCUMENTS VIEW
COFT - PDSD - PERMIT CARD.PDF DOCUMENTS VIEW
CBD-STRUCTURAL REVISION (DETAIL 2)-5639 E 5TH STREET-25-0612_V1.PDF DOCUMENTS VIEW
COFT - PDSD - PERMIT CARD.PDF DOCUMENTS VIEW
CONS-CONS-1_RAH BUNGALOW QUAD LIVING CD SET (FOURTH REVISION)_V4_V1.PDF DOCUMENTS VIEW
COFT - PDSD - PERMIT CARD.PDF DOCUMENTS VIEW
122286 QUAD LIVING 5TH CALC PACKAGE SEALED 221006_V1.PDF DOCUMENTS VIEW
22270 MJ_V1.PDF DOCUMENTS VIEW
CONS-3_RAH QUAD CD_V3.PDF DOCUMENTS VIEW
122286 QUAD LIVING 5TH CALC PACKAGE SEALED 221006_V1.PDF DOCUMENTS VIEW
22270 MJ_V1.PDF DOCUMENTS VIEW