Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Complete
Type:
Commercial Building
Address:
4777 E 29TH ST
Address NEW:
4777 E 29TH ST
Apply Date:
10/15/2024
Applicant:
Holly Spano
Description:
Upgrade (2) two existing 500kW generators to 750kW generators.

Permit Reviews

Permit Number - TC-COM-1024-01975
Permit Status: Complete
Permit Description: Upgrade (2) two existing 500kW generators to 750kW generators.
Start Date Submittal Complete Date Status  
10/15/2024 COMMERCIAL PDSD SIMPLE REVIEW v.1 10/16/2024 APPROVED Review Details

Conditions

Permit Number - TC-COM-1024-01975
Permit Status: Complete
Permit Description: Upgrade (2) two existing 500kW generators to 750kW generators.
Date Description Comments
10/16/2024 Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit. Contractor must have a TDC Online account and be added to the permit as a contact.

Outstanding Inspections

Permit Status: Complete
Permit Number: TC-COM-1024-01975
Permite Description: Upgrade (2) two existing 500kW generators to 750kW generators.
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
11/19/2024 COT - LCEL - Grounding/Bonding N/A Partial Pass Partial approval for Generator #1, 1/0 cu ground to existing Ufer
Pending Gen #2 grounding
11/15/2024 COT - LCEL - Electrical Intermediate N/A Not Ready 11/15/24: pre-construction meeting.

Completed Inspections

Permit Status: Complete
Permit Number: TC-COM-1024-01975
Permit Description: Upgrade (2) two existing 500kW generators to 750kW generators.
Total Completed Inspections - 5
Date Description Inspector Results Comments
12/09/2024 BULD - Electrical Clearance Passed Approved (2) new 500kw Generator #1 and #2, connected to existing panel #G - AG Clearance to TEP is required for unit #2
Pending final - NR
12/19/2024 COT - LCEL - Grounding/Bonding Passed 12/19/2024 approved. Gen #2 1/0 in place.
12/19/2024 COT - LCEL - Electrical Underground Passed Okay to backfill. Shading is required. 12/19/2024
12/19/2024 COT - LCEL - Electrical Intermediate Passed
12/19/2024 COT - LCEL - Electrical Final Passed Final approved. 12/19/2024

Documents

File Name Document Type  
24169-PDF-241014-COX TUCSON MTC GENERATOR REPLACEMENT-100_V1.PDF DOCUMENTS VIEW
COFT - PDSD - PERMIT CARD.PDF DOCUMENTS VIEW