Permit: TC-COM-0924-01708
Permit Details
Apply Date:
09/03/2024
Applicant:
jerry huckabee
Description:
Interior renovation to an existing JD Sports.
Permit Reviews
Permit Number - TC-COM-0924-01708
Permit Status: Issued
Permit Description: Interior renovation to an existing JD Sports.
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
10/21/2024 | COMMERCIAL REVIEW - FULL v.2 | 10/24/2024 | APPROVED |
10/24/2024 | RESTAMP - COMMERCIAL v.1 | 10/29/2024 | APPROVED |
09/09/2024 | COMMERCIAL REVIEW - FULL v.1 | 10/01/2024 | REQUIRES RESUBMIT |
10/29/2024 | RESTAMP - COMMERCIAL v.1 | 10/31/2024 | APPROVED |
01/03/2025 | BUILDING DEFERRED SUBMITTAL REVIEW v.1 | 01/09/2025 | REQUIRES RESUBMIT |
01/31/2025 | BUILDING DEFERRED SUBMITTAL REVIEW v.1 | 02/03/2025 | APPROVED |
01/27/2025 | BUILDING DEFERRED SUBMITTAL REVIEW v.2 | 01/28/2025 | APPROVED |
Conditions
Permit Number - TC-COM-0924-01708
Permit Status: Issued
Permit Description: Interior renovation to an existing JD Sports.
Date | Description | Comments |
---|---|---|
09/23/2024 | Please contact Pima County Addressing to resolve issue. Addressing@pima.gov or 520-724-9512 | |
10/24/2024 | AIR BALANCING REPORT IS REQUIRED. | |
09/09/2024 | Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit. Contractor must have a TDC Online account and be added to the permit as a contact. | |
01/03/2025 | Shelving Designs must be submitted and approved prior to final. | |
10/24/2024 | WATER STERILIZATION REPORT IS REQUIRED. |
Outstanding Inspections
Permit Status: Issued
Permit Number: TC-COM-0924-01708
Permite Description: Interior renovation to an existing JD Sports.
Total Outstanding Inspections - 11
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/03/2025 | BULD - Electrical Clearance | N/A | Not Applicable | |
01/03/2025 | COT - BULD - SWG Clearance | N/A | Not Applicable | |
01/03/2025 | PDSD Heavy Commercial Building Division Pre-Construction Meeting | N/A | Not Applicable | |
11/22/2024 | COT - HCBU - Framing | N/A | Partial Pass | 11/22/24: framing inspection passed at north and south sales floor area. West wall of sales area is not complete pending studs that are over spaced, fasteners missing at studs to bottom track at west wall and to backing at west wall, framing at entry not complete pending fasteners throughout. Ok to one side north and south wall at sales floor area. |
01/03/2025 | COT - HCBU - Masonry Pregrout | N/A | Not Applicable | |
01/03/2025 | COT - HCBU - Sustainability | N/A | Not Applicable | |
11/21/2024 | COT - HCEL - Electrical Intermediate | N/A | Partial Pass | 11/21/24: electrical underground per plans at main sales floor. |
01/28/2025 | COT - HCBU - CofO | N/A | Partial Pass | 1/28/25: ok for CofO. Pending fire final |
01/23/2025 | COT - FCON - Alarm - Final | N/A | Re-inspection required | Need to add smoke detector to base above FACP. |
01/28/2025 | COT - HCBU - Building Final | N/A | Partial Pass | 1/28/25: ok for CofO. Pending fire final |
01/23/2025 | COT - FCON - Fire - Final | N/A | Re-inspection required | Need to add smoke detector to base above FACP and address Exit lights. |
Completed Inspections
Permit Status: Issued
Permit Number: TC-COM-0924-01708
Permit Description: Interior renovation to an existing JD Sports.
Total Completed Inspections - 25