Permit Number: TC-COM-0924-01708
Parcel: 137055330

Review Status: Requires Resubmit

Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1

Permit Number - TC-COM-0924-01708
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/08/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/08/2025 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Deferred Submittal - Shelving

Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 1/8/2025 12:49:09 PM




Building(B) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 1/6/2025 1:13:35 AM
1. Storage layout shown in A00.3 code plan does not match partial floor plan and shelving layout in SH-1. Provided coordinated and updated A00.3.
2. 2018 IFC section 3201.2 listed item 9 shows to locate required fire department access doors. Show this in SH-1 and updated A00.3.
3. Show exit door swings in A00.3 and SH-1. 2018 IBC section 1010.0.2.1 Direction of swing. Pivot or side-hinged swinging doors shall swing in the direction of egress travel were serving a room or area containing an occupant load of 50 or more persons or a group H occupancy.
01/03/2025 PDSD Application Completeness Express REVIEW COMPLETED