Permit: TC-COM-0825-01546
Permit Details
Status:
Issued
Type:
Commercial Building
Address:
800 E UNIVERSITY BL UNIT 106
Address NEW:
800 E UNIVERSITY BL UNIT 106
Apply Date:
08/18/2025
Applicant:
Joshua Stewart
Description:
Remodel existing space for retail yogurt (Revision-2: Added Aerial Site Plan, white lattice fence panels at main façade (A201), framed panel over exist window & door)
Permit Reviews
Permit Number - TC-COM-0825-01546
Permit Status: Issued
Permit Description: Remodel existing space for retail yogurt (Revision-2: Added Aerial Site Plan, white lattice fence panels at main façade (A201), framed panel over exist window & door)
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 10/15/2025 | ADMINISTRATIVE v.2 | 10/15/2025 | APPROVED |
| 12/08/2025 | COMMERCIAL REVIEW - FULL REVISION v.1 | 01/05/2026 | APPROVED |
| 05/22/2026 | BUILDING DEFERRED SUBMITTAL REVIEW v.1 | 05/26/2026 | APPROVED |
| 04/28/2026 | BUILDING DEFERRED SUBMITTAL REVIEW v.1 | 04/30/2026 | APPROVED |
| 10/06/2025 | COMMERCIAL REVIEW - LIMITED v.3 | 10/07/2025 | APPROVED |
| 09/15/2025 | COMMERCIAL REVIEW - LIMITED v.2 | 10/03/2025 | REQUIRES RESUBMIT |
| 10/13/2025 | ADMINISTRATIVE v.1 | 10/13/2025 | REQUIRES RESUBMIT |
| 10/07/2025 | RESTAMP - COMMERCIAL v.1 | 10/13/2025 | APPROVED |
| 08/18/2025 | COMMERCIAL REVIEW - LIMITED v.1 | 09/03/2025 | REQUIRES RESUBMIT |
Conditions
Permit Number - TC-COM-0825-01546
Permit Status: Issued
Permit Description: Remodel existing space for retail yogurt (Revision-2: Added Aerial Site Plan, white lattice fence panels at main façade (A201), framed panel over exist window & door)
| Date | Description | Comments |
|---|---|---|
| 09/26/2025 | AIR BALANCING REPORT IS REQUIRED. | |
| 10/13/2025 | Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit. Contractor must have a TDC Online account and be added to the permit as a contact. | |
| 09/26/2025 | COUNTY HEALTH INSPECTION IS REQUIRED - PLEASE PROVIDE DOCUMENTATION THAT THE INSPECTION HAS BEEN COMPLETED AND PASSED. | |
| 08/18/2025 | Separate submittal to PC RWRD is required for new connections to sewer, new water meters and upsized water meters. For review and assessment: apply online at https://permits.pima.gov/ or contact us at sewer@pima.gov, (520) 724-9900. | |
| 08/18/2025 | Separate submittal to PC RWRD is required for new connections to sewer, new water meters and upsized water meters. For review and assessment: apply online at https://permits.pima.gov/ or contact us at sewer@pima.gov, (520) 724-9900. | |
| 09/26/2025 | WATER STERILIZATION REPORT IS REQUIRED. |
Outstanding Inspections
Permit Status: Issued
Permit Number: TC-COM-0825-01546
Permite Description: Remodel existing space for retail yogurt (Revision-2: Added Aerial Site Plan, white lattice fence panels at main façade (A201), framed panel over exist window & door)
Total Outstanding Inspections - 5
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/12/2025 | COT - HCPL - Sewer | N/A | Partial Pass | southeast side of suite about 35ft. |
| 04/27/2026 | BULD - Electrical Clearance | N/A | Not Applicable | |
| 04/27/2026 | COT - BULD - SWG Clearance | N/A | Not Applicable | |
| COT - FCON - Alarm - Final | N/A | Not Ready | ||
| 04/27/2026 | COT - LCBU - Building Final | N/A | Re-inspection required | 4/27/26: Grab bars shall be no higher than 36" AFF per A117.1 (609.4.1), Mirror must be installed to verify height, floor sinks shall be sealed with approved method to prevent sewer gases from escaping, exterior hose-bib must be insulated and wrapped from UV protection, Refrigerant lines for condenser must be appropriately supported, seal sleeve on south exterior wall, 90 degree elbow required on condensate drain, UV coat all exterior plastic piping, Refrigerant locking caps required at condenser, exterior receptacle shall be WR, water heater installed is 3-phase (plans call for single phase with approved e;electrical connection) ( 3-phase will not work for this application with single phase connections). |
Completed Inspections
Permit Status: Issued
Permit Number: TC-COM-0825-01546
Permit Description: Remodel existing space for retail yogurt (Revision-2: Added Aerial Site Plan, white lattice fence panels at main façade (A201), framed panel over exist window & door)
Total Completed Inspections - 19
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/12/2025 | COT - LCPL - Rough Soil | Passed | ||
| 11/14/2025 | COT - LCBU - Preslab | Passed | Okay for concrete placement. Both areas. Ada bathroom and front lobby. 11/14/2025 | |
| 12/10/2025 | COT - LCBU - Framing | Passed | Passed 12/10/25 | |
| 12/29/2025 | COT - LCEL - Electrical Intermediate | Passed | ||
| 01/21/2026 | COT - LCPL - Plumbing Intermediate | Passed | Domestic water lines at interior of structure. | |
| 01/21/2026 | COT - LCPL - Plumbing Above Ceiling | Passed | Ok to insulate hot water lines. | |
| 01/27/2026 | COT - HCPL - Sewer | Passed | ||
| 02/09/2026 | COT - LCME - Mechanical Above Ceiling | Passed | ||
| 02/09/2026 | COT - LCME - Mechanical Intermediate | Passed | ||
| 03/10/2026 | COT - HCEL - Electrical Underground | Passed | ||
| 04/27/2026 | ENGR Engineering Final | Passed | ||
| 04/27/2026 | COT - FCON - Fire - Final | Passed | ||
| 04/27/2026 | COT - LCME - Mechanical Final | Passed | ||
| 04/27/2026 | COT - LCEL - Electrical Final | Passed | ||
| 04/27/2026 | COT - LCPL - Plumbing Final | Passed | ||
| 04/27/2026 | COT - FCON - Sprinkler - Final | Passed | ||
| 04/27/2026 | COT - HCEL - Electrical Progress | Passed | ||
| 04/24/2026 | TRSP - ROW - Final/Close-Out | Passed | ||
| 04/29/2026 | COT - LCBU - Building Final | Passed | 4/29/2026 approved. All corrections were made. |