Permit Details

Status:
Inspections
Type:
Commercial Building
Apply Date:
08/28/2024
Applicant:
Ted Herman
Description:
FIT CULTR - Tenant improvement to an existing commercial masonry building. Building is to remain as it is with no additional square footage added. Use will be personal service.

Permit Reviews

Permit Number - TC-COM-0824-01682
Permit Status: Inspections
Permit Description: FIT CULTR - Tenant improvement to an existing commercial masonry building. Building is to remain as it is with no additional square footage added. Use will be personal service.
Start Date Submittal Complete Date Status  
08/30/2024 COMMERCIAL REVIEW - LIMITED v.1 09/17/2024 REQUIRES RESUBMIT Review Details
10/03/2024 RESTAMP - COMMERCIAL v.2 10/03/2024 APPROVED Review Details
09/19/2024 COMMERCIAL REVIEW - LIMITED v.2 09/26/2024 APPROVED Review Details
09/26/2024 RESTAMP - COMMERCIAL v.1 09/26/2024 REQUIRES RESUBMIT Review Details

Conditions

Permit Number - TC-COM-0824-01682
Permit Status: Inspections
Permit Description: FIT CULTR - Tenant improvement to an existing commercial masonry building. Building is to remain as it is with no additional square footage added. Use will be personal service.
Date Description Comments
10/09/2024 Sewer/Wastewater

Outstanding Inspections

Permit Status: Inspections
Permit Number: TC-COM-0824-01682
Permite Description: FIT CULTR - Tenant improvement to an existing commercial masonry building. Building is to remain as it is with no additional square footage added. Use will be personal service.
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
12/20/2024 COT - HCPL - Plumbing Intermediate N/A Partial Pass 12-20-24, plumbing intermediate verified as per approved plans and under test.
12/20/2024 COT - HCEL - Electrical Intermediate N/A Partial Pass 12-20-24, no more than 3 mc cables tied together, missing knockout on receptacle which is closer to the north wall, fire foam all penetrations, properly secure mc cable to rafters/joists. Receptacle layout along walls is per plans and construction along these areas is okay to continue. Reschedule inspection for the listed above items mentioned.

Scheduled Inspections

Scheduled Inspections - TC-COM-0824-01682
Status: Inspections
Description: FIT CULTR - Tenant improvement to an existing commercial masonry building. Building is to remain as it is with no additional square footage added. Use will be personal service.
Scheduled Date Description Entered By Entered Date
12/23/2024 COT - HCEL - Electrical Intermediate Scheduled
For information about today’s scheduled inspections please refer to the PDSD Daily Inspections Dashboards (Desktop) PDSD Daily Inspections Dashboards (Mobile) .

Documents

File Name Document Type  
COFT - PDSD - PERMIT CARD.PDF DOCUMENTS VIEW
CONS-FIT CULTR - SOLOT PLAZA_V2_V1.PDF DOCUMENTS VIEW