Inspection History Details
Inspection Status: Partial Pass
Inspection History: COT - HCEL - Electrical Intermediate
Permit Number - TC-COM-0824-01682
Inspection Description - COT - HCEL - Electrical Intermediate
Inspection Status - Partial Pass
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/20/2024 | COT - HCEL - Electrical Intermediate | Partial Pass | 12-20-24, no more than 3 mc cables tied together, missing knockout on receptacle which is closer to the north wall, fire foam all penetrations, properly secure mc cable to rafters/joists. Receptacle layout along walls is per plans and construction along these areas is okay to continue. Reschedule inspection for the listed above items mentioned. | |
COT - HCEL - Electrical Intermediate | Scheduled |