Permit: TC-COM-0824-01604
Permit Details
Status:
Approved
Type:
Commercial Building
Address:
2308 N CAMPBELL AV
Address NEW:
2308 N CAMPBELL AV
Apply Date:
08/15/2024
Applicant:
Andrew Venne
Description:
Roof Repairs for 2308 N Campbell Ave
Permit Reviews
Permit Number - TC-COM-0824-01604
Permit Status: Approved
Permit Description: Roof Repairs for 2308 N Campbell Ave
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 03/20/2026 | RESTAMP - COMMERCIAL v.1 | N/A | APPROVED |
| 08/15/2024 | COMMERCIAL REVIEW - FULL v.1 | 08/29/2024 | REQUIRES RESUBMIT |
| 10/10/2024 | COMMERCIAL REVIEW - FULL v.2 | 10/29/2024 | REQUIRES RESUBMIT |
| 10/30/2024 | COMMERCIAL REVIEW - FULL v.3 | 11/04/2024 | APPROVED |
Outstanding Activity Conditions
Permit Number - TC-COM-0824-01604
Permit Status: Approved
Permit Description: Roof Repairs for 2308 N Campbell Ave
Total Outstanding Activity Conditions - 2
| Date | Name |
|---|---|
| 09/26/2024 | SPECIAL INSPECTION FOR EPOXY ANCHORS IS REQUIRED. |
| 09/26/2024 | Post-Installed Anchor Inspection Report is required. |
Conditions
Permit Number - TC-COM-0824-01604
Permit Status: Approved
Permit Description: Roof Repairs for 2308 N Campbell Ave
| Date | Description | Comments |
|---|---|---|
| 08/15/2024 | Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit. Contractor must have a TDC Online account and be added to the permit as a contact. |
Outstanding Inspections
Permit Status: Approved
Permit Number: TC-COM-0824-01604
Permite Description: Roof Repairs for 2308 N Campbell Ave
Total Outstanding Inspections - 6
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/17/2026 | COT - FCON - Fire - Final | N/A | Not Applicable | |
| 03/17/2026 | ENGR Engineering Final | N/A | Not Ready | |
| 03/17/2026 | COT - HCBU - Building Above Ceiling | N/A | Re-inspection required | 3/17/26: legend C has not been completed per approved plans at east wall (currently no work was done at damaged truss), plans call for 3x12 beams for repairs (currently (2)2x12 installed), ensure all supports are appropriately spaced at beam repairs (48" o.c max), HGAM10KT missing throughout per approved plans, special inspection report must be sealed and completed prior to submission (currently only have intermediate documentation), replaced rood decking was never inspected prior to dry-in please provide documentation and letter from contractor ensuring all requirements of the 2018 IBC are met and provide all documents to portal. |
| 03/17/2026 | COT - HCBU - Building Final | N/A | Re-inspection required | 3/17/26: legend C has not been completed per approved plans at east wall (currently no work was done at damaged truss), plans call for 3x12 beams for repairs (currently (2)2x12 installed), ensure all supports are appropriately spaced at beam repairs (48" o.c max), HGAM10KT missing throughout per approved plans, special inspection report must be sealed and completed prior to submission (currently only have intermediate documentation), replaced rood decking was never inspected prior to dry-in please provide documentation and letter from contractor ensuring all requirements of the 2018 IBC are met and provide all documents to portal. |
| 03/17/2026 | COT - HCBU - Framing | N/A | Re-inspection required | 3/17/26: legend C has not been completed per approved plans at east wall (currently no work was done at damaged truss), plans call for 3x12 beams for repairs (currently (2)2x12 installed), ensure all supports are appropriately spaced at beam repairs (48" o.c max), HGAM10KT missing throughout per approved plans, special inspection report must be sealed and completed prior to submission (currently only have intermediate documentation), replaced rood decking was never inspected prior to dry-in please provide documentation and letter from contractor ensuring all requirements of the 2018 IBC are met and provide all documents to portal. |
| 03/17/2026 | COT - HCBU - Roof Nailing | N/A | Re-inspection required | 3/17/26: legend C has not been completed per approved plans at east wall (currently no work was done at damaged truss), plans call for 3x12 beams for repairs (currently (2)2x12 installed), ensure all supports are appropriately spaced at beam repairs (48" o.c max), HGAM10KT missing throughout per approved plans, special inspection report must be sealed and completed prior to submission (currently only have intermediate documentation), replaced rood decking was never inspected prior to dry-in please provide documentation and letter from contractor ensuring all requirements of the 2018 IBC are met and provide all documents to portal. |
Completed Inspections
Permit Status: Approved
Permit Number: TC-COM-0824-01604
Permit Description: Roof Repairs for 2308 N Campbell Ave
Total Completed Inspections - 1
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/17/2026 | TRSP - ROW - Notice of Completion | Passed | All work in the right away has been completed. The remainder of the work was all done inside the imagination. |