Permit Details

Status:
Issued
Type:
Commercial Building
Address NEW:
7000 S ALVERNON WY
Apply Date:
05/06/2025
Applicant:
Andrew Freeman
Description:
HVAC System upgrades

Permit Reviews

Permit Number - TC-COM-0525-00929
Permit Status: Issued
Permit Description: HVAC System upgrades
Start Date Submittal Complete Date Status  
03/25/2026 BUILDING DEFERRED SUBMITTAL REVIEW v.1 03/27/2026 APPROVED Review Details
09/24/2025 COMMERCIAL REVIEW - FULL v.2 10/14/2025 APPROVED Review Details
10/14/2025 RESTAMP - COMMERCIAL v.1 10/17/2025 APPROVED Review Details
05/12/2025 COMMERCIAL REVIEW - FULL v.1 06/04/2025 REQUIRES RESUBMIT Review Details

Conditions

Permit Number - TC-COM-0525-00929
Permit Status: Issued
Permit Description: HVAC System upgrades
Date Description Comments
06/03/2025 AIR BALANCING REPORT IS REQUIRED.
05/12/2025 Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit. Contractor must have a TDC Online account and be added to the permit as a contact.

Outstanding Inspections

Permit Status: Issued
Permit Number: TC-COM-0525-00929
Permite Description: HVAC System upgrades
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
01/05/2026 COT - LCPL - Plumbing Final N/A Not Ready 1/5/26: air gap required at condensate discharge at floor drain, properly secure electrical low-voltage wiring at all Units, all Exterior receptacles shall be tested at Final and be WR, labels required on all (disconnect boxes, units, panels, new circuit breaker at MSB), open all junction boxes to verify bond/bushings at raceways, verify wire size at MSB for new circuit, verify all metallic boxes are grounded, verify framing around new openings, all supports must be attached head to cable at flexible duct, condensate drain insulation must be protected from UV EXPOSURE. WILL BE VERIFIED AT FINAL.

Completed Inspections

Permit Status: Issued
Permit Number: TC-COM-0525-00929
Permit Description: HVAC System upgrades
Total Completed Inspections - 7
Date Description Inspector Results Comments
01/05/2026 COT - LCBU - Framing Passed
01/05/2026 COT - LCME - Mechanical Intermediate Passed
01/05/2026 COT - LCEL - Electrical Intermediate Passed
03/24/2026 COT - LCPL - Plumbing Final Passed 3-24-26: plumbing final approved.
03/24/2026 COT - LCME - Mechanical Final Passed 3-24-26: mechanical final approved.
03/24/2026 COT - LCEL - Electrical Final Passed 3-24-26: electrical final approved.
03/24/2026 COT - LCBU - Building Final Passed 3-24-26: building final approved.

Documents

File Name Document Type  
HOME GOODS SHIPPING WINGS TAB REPORT_V1.PDF DOCUMENTS VIEW
COFT - PDSD - PERMIT CARD.PDF DOCUMENTS VIEW
CONS-2025.09.16 - EMCOR HOMEGOODS TUCSON - PERMIT DOCS SHIPPING WING - CITY REVIEW COMMENTS_V2.PDF DOCUMENTS VIEW
HOMEGOODS DISTRIBUTION CENTER - SHIPPING WINGS - STRUCTURAL CALCULATIONS_V1_V2.PDF DOCUMENTS VIEW