Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: TC-COM-0524-00894
Permit Details
Apply Date:
05/08/2024
Applicant:
burak bekat
Description:
Tenant improvement for Roadies, a Family Entertainment Center with a bowling alley, arcade, axe throwing and laser tag
Permit Reviews
Permit Number - TC-COM-0524-00894
Permit Status: In review
Permit Description: Tenant improvement for Roadies, a Family Entertainment Center with a bowling alley, arcade, axe throwing and laser tag
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
12/12/2024 | COMMERCIAL REVIEW - FULL v.1 | N/A | IN REVIEW |
08/13/2024 | RESTAMP - COMMERCIAL v.1 | 08/15/2024 | APPROVED |
07/02/2024 | COMMERCIAL REVIEW - FULL v.2 | 08/13/2024 | APPROVED |
05/10/2024 | COMMERCIAL REVIEW - FULL v.1 | 06/17/2024 | REQUIRES RESUBMIT |
Outstanding Activity Conditions
Permit Number - TC-COM-0524-00894
Permit Status: In review
Permit Description: Tenant improvement for Roadies, a Family Entertainment Center with a bowling alley, arcade, axe throwing and laser tag
Total Outstanding Activity Conditions - 6
Date | Name |
---|---|
06/12/2024 | AIR BALANCING REPORT IS REQUIRED. |
06/12/2024 | WATER STERILIZATION REPORT IS REQUIRED. |
08/06/2024 | SPECIAL INSPECTION FOR EPOXY ANCHORS IS REQUIRED. |
08/06/2024 | SPECIAL INSPECTION FOR STEEL CONSTRUCTION IS REQUIRED. |
08/08/2024 | Guard designs at projector mezzanines shown . Designs must be submitted and approved, then installed prior to Final Inspections |
08/08/2024 | Plans to be revised to show Laser Tag room #114 comply with IBC Section 411. Approved directional exit markings shall be provided. Where mirrors, mazes or other designs are utilized that disguise the path of egress travel such that they are not apparent, approved and listed low-level exit signs that comply with Section 1013.5, and directional path markings listed in accordance with UL 1994, shall be provided and located not more than 8 inches (203 mm) above the walking surface and on or near the path of egress travel. Such markings shall become visible in an emergency. The directional exit marking shall be activated by the automatic fire detection system and the automatic sprinkler system in accordance with Section 907.2.11. |
Conditions
Permit Number - TC-COM-0524-00894
Permit Status: In review
Permit Description: Tenant improvement for Roadies, a Family Entertainment Center with a bowling alley, arcade, axe throwing and laser tag
Date | Description | Comments |
---|---|---|
05/10/2024 | Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit. Contractor must have a TDC Online account and be added to the permit as a contact. | |
08/06/2024 | Separate submittal to PC RWRD is required for new connections to sewer, new water meters and upsized water meters. Contact sewer@pima.gov for review and assessment. |
Outstanding Inspections
Permit Status: In Review
Permit Number: TC-COM-0524-00894
Permite Description: Tenant improvement for Roadies, a Family Entertainment Center with a bowling alley, arcade, axe throwing and laser tag
Total Outstanding Inspections - 7
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/08/2024 | COT - LCBU - Framing | N/A | Partial Pass | South Barge wall. |
10/14/2024 | COT - HCBU - Interior Shear Bracing | N/A | Partial Pass | Third layer on West Fire Wall. |
12/04/2024 | COT - LCEL - Electrical Above Ceiling | N/A | Partial Pass | Rooms #107,#108,#109,#110,#111. Approved okay to proceed progress areas. 12/4/2024 |
12/04/2024 | COT - LCME - Mechanical Above Ceiling | N/A | Partial Pass | Rooms #107,#108,#109,#110,#111. Approved okay to proceed progress areas. 12/4/2024 |
11/22/2024 | COT - LCBU - Masonry Pregrout | N/A | Canceled | Canceled per contractor. 11/22/2024 |
12/17/2024 | BULD - Electrical Clearance | N/A | Not Applicable | |
12/17/2024 | COT - BULD - SWG Clearance | N/A | Not Applicable |
Completed Inspections
Permit Status: In Review
Permit Number: TC-COM-0524-00894
Permit Description: Tenant improvement for Roadies, a Family Entertainment Center with a bowling alley, arcade, axe throwing and laser tag
Total Completed Inspections - 13
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/27/2024 | COT - LCPL - Rough Soil | Passed | ||
08/28/2024 | COT - LCEL - Electrical Underground | Passed | ||
09/10/2024 | COT - LCEL - Electrical Intermediate | Passed | ||
09/10/2024 | COT - LCBU - Excavation/Rebar/Zoning | Passed | ||
09/10/2024 | COT - LCBU - Preslab | Passed | ||
09/06/2024 | COT - HCPL - Rough Soil | Passed | ||
11/13/2024 | COT - LCBU - Framing | Passed | ||
11/13/2024 | COT - LCME - Mechanical Intermediate | Passed | ||
11/13/2024 | COT - LCEL - Electrical Progress | Passed | ||
11/13/2024 | COT - LCPL - Plumbing Intermediate | Passed | ||
11/13/2024 | COT - HCBU - Interior Shear Bracing | Passed | ||
11/19/2024 | COT - LCBU - Roof Nailing | Passed | ||
12/04/2024 | COT - LCBU - Masonry Pregrout | Passed |