Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: TC-COM-0524-00894
Permit Details
Apply Date:
05/08/2024
Applicant:
burak bekat
Description:
Tenant improvement for Roadies, a Family Entertainment Center with a bowling alley, arcade, axe throwing and laser tag
Permit Reviews
Permit Number - TC-COM-0524-00894
Permit Status: In review
Permit Description: Tenant improvement for Roadies, a Family Entertainment Center with a bowling alley, arcade, axe throwing and laser tag
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
03/05/2025 | BUILDING DEFERRED SUBMITTAL REVIEW v.1 | 03/07/2025 | APPROVED |
12/12/2024 | COMMERCIAL REVIEW - FULL v.1 | 01/08/2025 | APPROVED |
08/13/2024 | RESTAMP - COMMERCIAL v.1 | 08/15/2024 | APPROVED |
07/02/2024 | COMMERCIAL REVIEW - FULL v.2 | 08/13/2024 | APPROVED |
02/19/2025 | BUILDING DEFERRED SUBMITTAL REVIEW v.1 | 02/25/2025 | REQUIRES RESUBMIT |
05/10/2024 | COMMERCIAL REVIEW - FULL v.1 | 06/17/2024 | REQUIRES RESUBMIT |
03/10/2025 | BUILDING DEFERRED SUBMITTAL REVIEW v.2 | N/A | IN REVIEW |
Outstanding Activity Conditions
Permit Number - TC-COM-0524-00894
Permit Status: In review
Permit Description: Tenant improvement for Roadies, a Family Entertainment Center with a bowling alley, arcade, axe throwing and laser tag
Total Outstanding Activity Conditions - 5
Date | Name |
---|---|
06/12/2024 | AIR BALANCING REPORT IS REQUIRED. |
08/06/2024 | SPECIAL INSPECTION FOR EPOXY ANCHORS IS REQUIRED. |
08/06/2024 | SPECIAL INSPECTION FOR STEEL CONSTRUCTION IS REQUIRED. |
08/08/2024 | Plans to be revised to show Laser Tag room #114 comply with IBC Section 411. Approved directional exit markings shall be provided. Where mirrors, mazes or other designs are utilized that disguise the path of egress travel such that they are not apparent, approved and listed low-level exit signs that comply with Section 1013.5, and directional path markings listed in accordance with UL 1994, shall be provided and located not more than 8 inches (203 mm) above the walking surface and on or near the path of egress travel. Such markings shall become visible in an emergency. The directional exit marking shall be activated by the automatic fire detection system and the automatic sprinkler system in accordance with Section 907.2.11. |
12/31/2024 | Guard designs at projector mezzanines shown . Designs must be submitted and approved, then installed prior to Final Inspections |
Conditions
Permit Number - TC-COM-0524-00894
Permit Status: In review
Permit Description: Tenant improvement for Roadies, a Family Entertainment Center with a bowling alley, arcade, axe throwing and laser tag
Date | Description | Comments |
---|---|---|
05/10/2024 | Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit. Contractor must have a TDC Online account and be added to the permit as a contact. | |
08/06/2024 | Separate submittal to PC RWRD is required for new connections to sewer, new water meters and upsized water meters. Contact sewer@pima.gov for review and assessment. | |
06/12/2024 | WATER STERILIZATION REPORT IS REQUIRED. |
Outstanding Inspections
Permit Status: In Review
Permit Number: TC-COM-0524-00894
Permite Description: Tenant improvement for Roadies, a Family Entertainment Center with a bowling alley, arcade, axe throwing and laser tag
Total Outstanding Inspections - 9
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/08/2024 | COT - LCBU - Framing | N/A | Partial Pass | South Barge wall. |
10/14/2024 | COT - HCBU - Interior Shear Bracing | N/A | Partial Pass | Third layer on West Fire Wall. |
11/22/2024 | COT - LCBU - Masonry Pregrout | N/A | Canceled | Canceled per contractor. 11/22/2024 |
12/17/2024 | BULD - Electrical Clearance | N/A | Not Applicable | |
12/17/2024 | COT - BULD - SWG Clearance | N/A | Not Applicable | |
03/06/2025 | COT - FCON - Sprinkler - Final | N/A | Partial Pass | Need to add the following. 1. FDC Knox Caps. 2. Suite number sign with FDC sign. 3. Repair Bell. 4. Add Riser Room sign to door. |
03/06/2025 | COT - HCBU - TCO | N/A | Partial Pass | OK for Level Two. |
03/07/2025 | ENGR Engineering Final | N/A | Partial Pass | TCO2 only is approved |
03/07/2025 | COT - LCME - Mechanical Final | N/A | Partial Pass | pending balance report approval |
Completed Inspections
Permit Status: In Review
Permit Number: TC-COM-0524-00894
Permit Description: Tenant improvement for Roadies, a Family Entertainment Center with a bowling alley, arcade, axe throwing and laser tag
Total Completed Inspections - 22