Permit Details

Status:
Issued
Type:
Commercial Building
Address NEW:
5919 E BROADWAY BL
Apply Date:
03/31/2023
Applicant:
Amy Hodgson
Description:
Interior tenant improvement for a new retail tenant Bullfrog Spas to move into an existing space. Scope to include new overhead door and minor electrical upgrades.

Permit Reviews

Permit Number - TC-COM-0323-00938
Permit Status: Issued
Permit Description: Interior tenant improvement for a new retail tenant Bullfrog Spas to move into an existing space. Scope to include new overhead door and minor electrical upgrades.
Start Date Submittal Complete Date Status  
06/05/2023 COMMERCIAL REVIEW - FULL v.2 06/05/2023 APPROVED Review Details
09/21/2023 COMMERCIAL REVIEW - FULL v.1 02/28/2024 REQUIRES RESUBMIT Review Details
03/28/2024 COMMERCIAL REVIEW - FULL v.2 06/27/2024 APPROVED Review Details
06/27/2024 RESTAMP - COMMERCIAL v.1 06/27/2024 APPROVED Review Details
04/05/2023 COMMERCIAL REVIEW - FULL v.1 05/26/2023 REQUIRES RESUBMIT Review Details
06/05/2023 RESTAMP - COMMERCIAL v.1 06/12/2023 APPROVED Review Details

Outstanding Activity Conditions

Permit Number - TC-COM-0323-00938
Permit Status: Issued
Permit Description: Interior tenant improvement for a new retail tenant Bullfrog Spas to move into an existing space. Scope to include new overhead door and minor electrical upgrades.
Total Outstanding Activity Conditions - 7
Date Name
05/26/2023 Special inspections must be performed by an approved third party inspection agency at the owner's expense. Special inspection forms and reports are required to be submitted for review and approved prior to issuance of final approval documents.
05/26/2023 SPECIAL INSPECTION FOR CONCRETE INSTALLATION IS REQUIRED.
05/26/2023 SPECIAL INSPECTION FOR EPOXY ANCHORS IS REQUIRED.
05/26/2023 SPECIAL INSPECTION FOR EXPANSION ANCHORS IS REQUIRED.
05/26/2023 SPECIAL INSPECTION FOR FIELD WELDING IS REQUIRED.
05/26/2023 SPECIAL INSPECTION FOR HIGH STRENGTH BOLTING IS REQUIRED.
05/26/2023 SPECIAL INSPECTION FOR SPECIAL GRADING, EXCAVATION AND FILLING IS REQUIRED.

Conditions

Permit Number - TC-COM-0323-00938
Permit Status: Issued
Permit Description: Interior tenant improvement for a new retail tenant Bullfrog Spas to move into an existing space. Scope to include new overhead door and minor electrical upgrades.
Date Description Comments
05/26/2023 Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit.
05/26/2023 Plan review applications expire 180 days from date of submittal unless the permit has been issued. Permits expire 180 days after issuance or last approved inspection.

Outstanding Inspections

Permit Status: Issued
Permit Number: TC-COM-0323-00938
Permite Description: Interior tenant improvement for a new retail tenant Bullfrog Spas to move into an existing space. Scope to include new overhead door and minor electrical upgrades.
Total Outstanding Inspections - 6
Last Inspection Date Description Inspector Results Comments
07/11/2023 COT - LCBU - Building Progress N/A Partial Pass 7/11/23: Met Felipe at site and reviewed approved drawings and I pointed out that a 3rd party inspector will be required for cutting a large opening into the rear CMU wall.
07/25/2023 COT - HCBU - Framing N/A Re-inspection required
09/14/2023 COT - HCEL - Electrical Above Ceiling N/A Partial Pass 9/13/23: remove all ceiling tiles in areas that require above ceiling inspection. Approved plans are required on site at all times.
9/14/23: above ceiling approved in wet spa display room on east wall.
09/26/2023 COT - HCEL - Electrical Final N/A Partial Pass 9/26/23: electric complete except for retyping panel schedules
10/03/2023 ENGR Engineering Final N/A Not Ready Additional ramp has been added to the exterior of the building, which blocks the pedestrian pathway from the other portions of the building to the trash and closure. This ramp needs to be submitted and approved by engineering and zoning, was for it can be inspected for the site.
10/13/2023 COT - FCON - Fire - Final N/A Partial Pass Exit sign in back hall way needs to be repaired, Exit sign in backroom needs to be repaired, Knox box, Knox FDC caps. Fire sprinkler work needs to be inspected, riser needs annual inspection.

Completed Inspections

Permit Status: Issued
Permit Number: TC-COM-0323-00938
Permit Description: Interior tenant improvement for a new retail tenant Bullfrog Spas to move into an existing space. Scope to include new overhead door and minor electrical upgrades.
Total Completed Inspections - 6
Date Description Inspector Results Comments
07/28/2023 COT - HCEL - Electrical Intermediate Passed Electrical rough-in is complete. Okay to cover walls with drywall.
07/28/2023 COT - HCBU - Framing Passed Bracing has been installed from rafters to top of wall on center wall. Okay to install drywall throughout building.
10/11/2023 COT - HCBU - Excavation/Rebar/Zoning Passed
10/13/2023 COT - FCON - Alarm - Final Passed Approved on 10/02/23 on permit TF-FCP-0923-01078.
10/17/2023 COT - HCBU - Building Final Passed Recommend Level 4 TCO.
11/14/2023 COT - FCON - Fire - Final Passed

Documents

File Name Document Type  
COFT - PDSD - PERMIT CARD.PDF DOCUMENTS VIEW
CONS-BULLFROG 5919 E BROADWAY- CD SET 12.6.23_V1.PDF DOCUMENTS VIEW
CONS-BULLFROG 5919 E BROADWAY- CD SET 5.4.23_V2.PDF DOCUMENTS VIEW
COFO_TEMPORARYCOFO.PDF DOCUMENTS VIEW
COFO_TEMPORARYCOFO.PDF DOCUMENTS VIEW
COFO_TEMPORARYCOFO.PDF DOCUMENTS VIEW
CONS-BULLFROG 5919 E BROADWAY- CD SET 5.4.23_V2.PDF DOCUMENTS VIEW
COFT - PDSD - PERMIT CARD.PDF DOCUMENTS VIEW
STANTEC_SPEC_INSP_CERT-2023-05-26_V1.PDF DOCUMENTS VIEW
CONS-STANTEC_APPROVED_PLANS_V1.PDF DOCUMENTS VIEW
CITY COMMENTS RESPONSE LETTER 6.2.23_V1.PDF DOCUMENTS VIEW
STANTEC_APPROVED_CALCS_STRUCT_V1.PDF DOCUMENTS VIEW
3RD PARTY REVIEW FORM_TUC_PSA_V2.PDF DOCUMENTS VIEW