Permit: TC-COM-0125-00146
Permit Details
Status:
Complete
Type:
Commercial Building
Address:
2662 N ALVERNON WY BLDG D
Address NEW:
2662 N ALVERNON WY BLDG D
Apply Date:
01/22/2025
Applicant:
Description:
Building D. Remove and replace all interior load centers in each unit with like for like
Permit Reviews
Permit Number - TC-COM-0125-00146
Permit Status: Complete
Permit Description: Building D. Remove and replace all interior load centers in each unit with like for like
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 01/24/2025 | COMMERCIAL PDSD SIMPLE REVIEW v.1 | 01/27/2025 | REQUIRES RESUBMIT |
| 02/13/2025 | RESTAMP - COMMERCIAL v.1 | 02/13/2025 | APPROVED |
| 02/13/2025 | COMMERCIAL PDSD SIMPLE REVIEW v.2 | 02/13/2025 | APPROVED |
Conditions
Permit Number - TC-COM-0125-00146
Permit Status: Complete
Permit Description: Building D. Remove and replace all interior load centers in each unit with like for like
| Date | Description | Comments |
|---|---|---|
| 01/24/2025 | Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit. Contractor must have a TDC Online account and be added to the permit as a contact. |
Outstanding Inspections
Permit Status: Complete
Permit Number: TC-COM-0125-00146
Permite Description: Building D. Remove and replace all interior load centers in each unit with like for like
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/11/2025 | COT - LCEL - Electrical Intermediate | N/A | Partial Pass | Approved interior sub-panel replacements for Building D, units #109, #111- #122, units #209 - #223, #225 - #233 (36) No electrical clearances are required |
| 07/17/2025 | COT - LCEL - Electrical Final | N/A | Re-inspection required | 7/9/25 - Approved interior sub-panel replacements for Building D, units #100 - #108, units #137, #138, #141, #142, units #200 - #208, units #237 - #242 (28) No electrical clearances are required 7/11/25 - Approved interior sub-panel replacements for Building D, units #109, #111- #122, units #209 - #223, #225 - #233 (36) No electrical clearances are required 7/15/2025 canceled per contractor. 7/17/25: wiring must be properly marked at terminals, #6 AWG copper required at all load centers for a 50Amp breaker (Rick stated it was a #8 AWG) |
Completed Inspections
Permit Status: Complete
Permit Number: TC-COM-0125-00146
Permit Description: Building D. Remove and replace all interior load centers in each unit with like for like
Total Completed Inspections - 1
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/29/2025 | COT - LCEL - Electrical Final | Passed | Approved per G.A. 7/29/2025 |