Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address NEW:
6624 E CALLE LA PAZ
Apply Date:
12/06/1999
Applicant:
ANDROS REFRIGERATION INC ,
Description:
AIR COND & HEAT:REPLACEMENT
Contractors:
  • ANDROS REFRIGERATION INC ,

Outstanding Inspections

Permit Status: Expired
Permit Number: T99ME01358
Permite Description: AIR COND & HEAT:REPLACEMENT
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
01/24/2000 MECHANICAL - FINAL N/A Correction Required ADDTL COMMS - 1. ANCHOR A/C EQUIPMENT AS PER SEC 304.4 UMC 2. 35 AMP FUSES ARE TOO LARGE 30 AMP MAX. 3. TERMINATE DRAIN LINE INTO A 2 MIN VENT USE AN APPROVED FITTING. DONT DRILL THE SIDE OF THE VENT AND STICK THE DRAIN PIPE INSIDE THE HOLE. MAKE NECESSARY CORRECTIONS AND RECALL FOR FINAL INSPECTION

Documents

File Name Document Type  
None DOCUMENTS VIEW