Permit: T99ME01358
Permit Details
Status:
Expired
Type:
SINGLE FAMILY OTHER
Address:
6624 E CALLE LA PAZ
Address NEW:
6624 E CALLE LA PAZ
Apply Date:
12/06/1999
Applicant:
ANDROS REFRIGERATION INC ,
Description:
AIR COND & HEAT:REPLACEMENT
Contractors:
- ANDROS REFRIGERATION INC ,
Outstanding Inspections
Permit Status: Expired
Permit Number: T99ME01358
Permite Description: AIR COND & HEAT:REPLACEMENT
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/24/2000 | MECHANICAL - FINAL | N/A | Correction Required | ADDTL COMMS - 1. ANCHOR A/C EQUIPMENT AS PER SEC 304.4 UMC 2. 35 AMP FUSES ARE TOO LARGE 30 AMP MAX. 3. TERMINATE DRAIN LINE INTO A 2 MIN VENT USE AN APPROVED FITTING. DONT DRILL THE SIDE OF THE VENT AND STICK THE DRAIN PIPE INSIDE THE HOLE. MAKE NECESSARY CORRECTIONS AND RECALL FOR FINAL INSPECTION |