Inspection Status: Correction Required
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/24/2000 |
MECHANICAL - FINAL |
|
Correction Required |
ADDTL COMMS - 1. ANCHOR A/C EQUIPMENT AS PER SEC 304.4 UMC 2. 35 AMP FUSES ARE TOO LARGE 30 AMP MAX. 3. TERMINATE DRAIN LINE INTO A 2 MIN VENT USE AN APPROVED FITTING. DONT DRILL THE SIDE OF THE VENT AND STICK THE DRAIN PIPE INSIDE THE HOLE. MAKE NECESSARY CORRECTIONS AND RECALL FOR FINAL INSPECTION |
| 01/24/2000 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999* |