Permit Details

Status:
Closed
Type:
COMMERCIAL OTHER
Apply Date:
12/28/1999
Applicant:
DIAMOND MANAGEMENT INC 32% & AUR
Description:
2 HR INSPECT FOR EMERGENCY REPAIR 5TH FLOOR

Completed Inspections

Permit Status: Closed
Permit Number: T99EL03318
Permit Description: 2 HR INSPECT FOR EMERGENCY REPAIR 5TH FLOOR
Total Completed Inspections - 3
Date Description Inspector Results Comments
12/30/1999 ELECTRIC - FINAL RMAJUTA Approved IVRS - Inspection 0000*
12/30/1999 ELECTRIC - FINAL RSUBA Approved IVRS - Inspection 0999*
12/30/1999 ELECTRIC - FINAL RSUBA Approved ADDTL COMMS - 1. GOUND JUMPERS ARE TO BE INSTALLED ON TOP END AND BOTTOM END OF NEW SECTION OF BUS DUCT (OUTSIDE FRAME OK SIZE) TO NEC 96 250 REQUIREMENTS. THIS IS TO BE COMPLETED WITHIN 24 HRS 2. 15 DAYS (WORKING) ARE GIVEN TILL ELECTRICAL ENGINEER HAS TO SUBMIT DRAWINGS TO DEVELPMENTS SERVICES CENTER FOR REVIEW 3. ENTIRE ELECT SUPPLY SYSTEM TO BE CHECKED FOR OPERATION FOR SAFETY OK WITHIN 15 DAYS 4. PROVIDE OK ON DRAWINGS FOR ONLY BOLTING SECTIONS OF BUSS TOGETHER (BOLTS ONLY TIGHETNED INTO COPPER BUS WITHOUT NUTS 5. IF THESE ITEMS CANNOT BE COMPLETED W/IN TIME REQUESTED NOTIFY BUIKDING OFFICIAL DAVE MANN CALLED AHEAD TO MEET ME HERE 5TH FLOOR ELEC. RM. EQUIP NOT OPENED AS REQUESTED PANEL IS LICKED