Inspection History Details
Inspection Status: Closed
Inspection History: ELECTRIC - FINAL
Permit Number - T99EL03318
Inspection Description - ELECTRIC - FINAL
Inspection Status - Closed
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/24/2008 | ELECTRIC - FINAL | Closed | REPAIRS MADE PER COMMENTS AT SOME POINT IN PAST | |
12/30/1999 | ELECTRIC - FINAL | Correction Required | ADDTL COMMS - 1. GOUND JUMPERS ARE TO BE INSTALLED ON TOP END AND BOTTOM END OF NEW SECTION OF BUS DUCT (OUTSIDE FRAME OK SIZE) TO NEC 96 250 REQUIREMENTS. THIS IS TO BE COMPLETED WITHIN 24 HRS 2. 15 DAYS (WORKING) ARE GIVEN TILL ELECTRICAL ENGINEER HAS TO SUBMIT DRAWINGS TO DEVELPMENTS SERVICES CENTER FOR REVIEW 3. ENTIRE ELECT SUPPLY SYSTEM TO BE CHECKED FOR OPERATION FOR SAFETY OK WITHIN 15 DAYS 4. PROVIDE OK ON DRAWINGS FOR ONLY BOLTING SECTIONS OF BUSS TOGETHER (BOLTS ONLY TIGHETNED INTO COPPER BUS WITHOUT NUTS 5. IF THESE ITEMS CANNOT BE COMPLETED W/IN TIME REQUESTED NOTIFY BUIKDING OFFICIAL DAVE MANN CALLED AHEAD TO MEET ME HERE 5TH FLOOR ELEC. RM. EQUIP NOT OPENED AS REQUESTED PANEL IS LICKED | |
12/30/1999 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* | |
12/30/1999 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* |